Chapter 2 - Operation
35
2.5.2
Operation via Control Terminal
1. Check the LCD display when Power ON. Otherwise, change the setting indicated above.
2. Turn the FX (or RX) terminal ON. Then FWD (or REV) LED will be lit.
3. Set the frequency using V1 (Potentiometer). Output freq (60Hz)., Rotating direction (FWD or REV) and output
current (5A) will be displayed on the LCD.
4. Output freq value is decreasing when turning the potentiometer counterclockwise. Inverter output stops at 0.00Hz
and motor is stopped.
5. Turn FX (or RX) terminal OFF.
Setting: DRV-03
[Drive Mode (Run/Stop method)] =
1 (Fx/Rx-1)
DRV-04
[Frequency Mode (Freq. setting method)] =
2 (V1)
DRV▶T/V 0.0 A
00 STP 0.00Hz
DRV▶T/V 0.0 A
00 FWD 0.00Hz
DRV▶T/V 5.0 A
00 FWD 60.00Hz
DRV▶T/V 0.0 A
00 FWD 0.00Hz
DRV▶T/V 0.0 A
00 STP 0.00Hz