Chapter 6 - Parameter Description [FU2]
99
6.3 Function 2 Group [FU2]
FU2-00: Jump to desired code #
Jumping directly to any parameter code can be
accomplished by entering the desired code number. This
code is available only with LCD keypad.
FU2-01: Previous Fault History 1
FU2-02: Previous Fault History 2
FU2-03: Previous Fault History 3
FU2-04: Previous Fault History 4
FU2-05: Previous Fault History 5
FU2-06: Erase Fault History
□
□
□
This code displays up to five previous fault (trip) status of
the inverter. Use the
PROG
,
? and ?
key before
pressing the
RESET
key to check the fault content(s),
output frequency, output current, and whether the
inverter was accelerating, decelerating, or in constant
speed at the time of the fault occurred. Press the
ENT
key to exit. The fault content will be stored in FU2-01
through FU2-05 when the
RESET
key is pressed. For
more detail, please refer to Chapter 7.
[Fault Contents]
Keypad Display
Fault (Trip)
LCD
7-Segment
Over-Current 1
Over Current 1
OC
Over-Voltage
Over Voltage
OV
External Trip Input A
External-A
EXTA
Emergency Stop
(Not Latched)
BX
BX
Low-Voltage
Low Voltage
LV
Fuse Open
Fuse Open
FUSE
Ground Fault
Ground Fault
GF
Over-Heat on Heat sink
Over Heat
OH
Electronic Thermal Trip
E-Thermal
ETH
Over-Load Trip
Over Load
OLT
Inverter H/W Fault
- EEP Error
- ADC Offset
- WDOG Error
- In-Phase Open
HW-Diag
HW
External Trip Input B
External-B
EXTB
Over-Current 2
Arm Short
ASHT
Option Error
Option
OPT
Output Phase Loss
Phase Open
PO
Inverter Over-Load
Inv. OLT
IOLT
☞
Note:
There are WDOG error, EEP error, and ADC
Offset for the inverter Hardware Fault, and the inverter
will not reset when H/W fault occurs. Repair the fault
before turning on the power.
☞
Note:
When multiple faults occur, only the highest-level
fault will be displayed.
This function erases all fault histories of FU2-01 to FU-
05 from the memory.
FU2? Jump code
00 1
Factory Default:
1
Related Functions:
DRV-12 [Fault Display] displays current
fault status.
FU2? Last trip-1
01 None
0
01
Factory Default:
None
0
FU2? Last trip-5
05 None
0
05
Factory Default:
None
0
FU2? Erase trips
06 --- No ---
05 None
0
06
Factory Default:
No
0
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 [email protected]