Chapter 6 - Parameter Description [FU1]
96
[Load Current Derating Curve]
☞
Note:
Despite the motor current changing frequently due
to load fluctuation or acceleration and deceleration, the
inverter calculates the i
2
t
and accumulates the value to
protect the motor.
FU1-54: Overload Warning Level
FU1-55: Overload Warning Time
The inverter generates an alarm signal when the output
current has reached the FU1-54 [Overload Warning
Level] for the FU1-55 [Overload Warning Time]. The
alarm signal persists for the FU1-55 even if the current
has become the level below the FU1-54.
Multi-function output terminal (AXA-AXC) is used as the
alarm signal output. To output the alarm signal, set I/O
44 [Multifunction Auxiliary Contact Output] to ‘OL’.
☞
Note:
Inverter is not tripped by this function.
☞
Note:
The set value is the percentage of FU2-33 [Rated
Motor Current].
[Overload Warning]
FU1-56: Overload Trip Selection
FU1-57: Overload Trip Level
FU1-58: Overload Trip Delay Time
Inverter cuts off its output and displays fault message
when the output current persists over the FU1-57
[Overload Trip Level] for the time of FU1-58 [Overload
Trip Time]. This function protects the inverter and motor
from abnormal load conditions.
100%
95%
65%
Output Current
20Hz
60Hz
Self-Cool
Forced-Cool
Related Functions:
FU2-33 [Rated Motor Current]
FU1? OL level
54 150 %
150
54
Factory Default:
150 %
150
FU1? OL time
55 10.0 sec
10.0
55
Factory Default:
10.0 sec
10.0
t1: FU1-55 [Overload Warning Time]
Output Current
Time
Time
FU1-54
[OL Level]
FU1-54
[OL Level]
AXA-AXC
ON
t1
t1
Related Functions:
FU2-33 [Rated Motor Current]
I/O-44 [Multi-function Auxiliary Contact
Output]
FU1? OLT select
56 --- Yes ---
1
56
Factory Default:
Yes
1
FU1? OLT level
57 180 %
180
57
Factory Default:
180 %
180
FU1? OLT time
58 60.0 sec
60.0
58
Factory Default:
60.0 sec
60.0