Chapter 6 - Parameter Description [I/O]
119
This is the filtering time constant for ‘I’ signal input. If the
‘I’ signal is affected by noise causing unstable operation
of the inverter, increase this value. Increasing this value
makes response time slower.
This is the minimum current of the ‘I’ input at which
inverter outputs minimum frequency.
This is the inverter output minimum frequency when
there is minimum current (I/O-07) on the ‘I’ terminal. In
torque mode, the display is changed to [%].
This is the maximum current of the ‘I’ input at which
inverter outputs maximum frequency.
This is the inverter output maximum frequency when
there is the maximum current (I/O-09) on the ‘I’ terminal.
In torque mode, the display is changed to [%].
Setting FU2-39 [Control mode select] to Vector_Torque
or Sensorless_T, the setting value is changed to Torque
value as below;
Code
Default
Setting
Code
Default
Setting
I/O-07
4 [mA] 0 ~ 20[mA]
I/O-09
20[mA] 0 ~ 20[mA]
I/O-08
0 [%]
0 ~ 150[%]
I/O-10
100[%] 0 ~ 150[%]
[Reference Frequency vs. Analog Current Input, I (4 to 20mA)]
I/O-11: Criteria for Analog Input Signal Loss
This is to set the criteria for analog input signal loss
when DRV-04 [Frequency Mode] is set to ‘V1’, ‘I’ or
‘V1+I’. Following table shows the setting value.
Setting Range
LCD
7-Seg
Description
None
0
Does not check the analog input signal.
half of x1
1
The inverter determines that the frequency
reference is lost when the analog input
signal is less than half of the minimum
value (I/O-02 or I/O-07).
below x1
2
The inverter determines that the frequency
reference is lost when the analog input
signal is less than the minimum value (I/O-
02 or I/O-07).
When the analog input signal is lost, inverter displays the
following table.
Setting
LCD 7-Seg
Description
LOP
PL
Loss of frequency reference from Option Board
(DPRAM time out)
LOR
RL
Loss of frequency reference from Option Board
(Communication fault)
LOV
VL
Loss of analog input signal, V1
LOI
IL
Loss of analog input signal, I
LOX
XL
Loss of frequency reference from Sub-Board, V2 or
ENC
Related Functions:
I/O-48 [Lost command] selects the
operation after determining the loss of frequency
reference.
I/O? I filter
06 10 ms
10
06
Factory Default:
10 ms
10
I/O? I curr x1
07 4.00 mA
4.00
07
Factory Default:
4.00 mA
4.00
I/O? I freq y1
08 0.00 Hz
0.00
08
Factory Default:
0.00 Hz
0.00
I/O? I curr x2
09 20.00 mA
20.00
09
Factory Default:
20.00 mA
20.00
I/O? I freq y2
10 60.00 Hz
60.00
10
Factory Default:
60.00 Hz
60.00
Reference Frequency
I/O-10
Analog Voltage
Input (V1)
I/O-08
I/O-07
I/O-09
Related Functions:
DRV-04 [Frequency Mode]
FU1-20 [Maximum Frequency]
I/O? Wire broken
11 None
0
11
Factory Default:
None
0
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 [email protected]