Zone Control
For zone control, up to eight (8) indoor units with a maximum capacity of 54,000 Btu/h can be connected to one port on the heat recovery
unit. Y-Branches or Headers can be used, depending on what is best for the application.
Maximum eight (8) Indoor Units
Indoor Unit Indoor Unit
Indoor Unit
Heat Recovery Unit 1
Outdoor Unit
Header
Indoor Unit
Heat Recovery Unit 2
Indoor Unit Y-Branches
Brazed Cap
Same Mode
Maximum eight (8) Indoor Units
Same Mode
Zone Control Group 2
Zone Control Group 1
Indoor Unit
Auto Changeover
• One heat recovery unit branch pipe can support a maximum of 54,000 Btu/h total indoor unit cooling capacity.
• PRHR041A heat recovery unit can support a maximum of 192,000 Btu/h total capacity and up to 32 connected indoor units (maximum
indoor units per heat recovery unit branch pipe is 8).
• Zone control groups cannot operate in “Auto changeover” or “Mode override” functions.
• In the zone control group, if some indoor units are operating in cooling or heating mode, the other indoor units cannot change over to /
operate in the opposite mode.
Y-Branch
Indoor Unit
Keep the sum of total Indoor Unit capacity under 192,000 Btu/h.
Heat Recovery Unit
Heat Recovery Unit
Outdoor Unit
Heat Recovery Unit
Heat Recovery Unit
Heat Recovery Unit
Heat Recovery Unit
Heat Recovery Unit
Indoor Unit Indoor Unit Indoor Unit
Indoor Unit Indoor Unit Indoor Unit Indoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
Keep the sum of total Indoor Unit capacity under 192,000 Btu/h.
Sample Layouts, Continued.
Sample Layouts
INSTALLING FOR HEAT RECOVERY
OPERATION
Images are for illustrative purposes only and are not accurate representations. For specific details on piping limitations and other refrigerant system
rules, review the information in this entire piping section, see the Multi V 5 Engineering Manual, and follow the LATS diagram.