SPECIFICATIONS
208 / 230V Outdoor Units
Table 2: Single Frame 208-230V Outdoor Units, continued.
Unit Model Number
ARUM168BTE5
14.0 Ton
ARUM192BTE5
16.0 Ton
ARUM216BTE5
18.0 Ton
ARUM241BTE5
20.0 Ton
Individual Component Model Numbers
-
-
-
-
Cooling Performance
Nominal Cooling Capacity (Btu/h)
1
168,000
192,000
216,000
240,000
Rated Cooling Capacity (Btu/h)
2
160,000
184,000
206,000
222,000
Heating Performance
Nominal Heating Capacity (Btu/h)
1
189,000
216,000
243,000
243,000
Rated Heating Capacity (Btu/h)
2
180,000
206,000
230,000
230,000
Operating Range
Cooling (°F DB)
5 to 122
5 to 122
5 to 122
5 to 122
Heating (°F WB)
-13 to +61
-13 to +61
-13 to +61
-13 to +61
Synchronous — Cooling Based (°F DB)
14 to 81
14 to 81
14 to 81
14 to 81
Synchronous — Heating Based (°F WB)
14 to 61
14 to 61
14 to 61
14 to 61
Compressor
Inverter Quantity
HSS DC Scroll x 2
HSS DC Scroll x 2
HSS DC Scroll x 2
HSS DC Scroll x 2
Oil/Type
PVE / FVC68D
PVE / FVC68D
PVE / FVC68D
PVE / FVC68D
Fan (Top Discharge)
Type
Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
Motor Output (kW) x Qty.
0.9 x 2
0.9 x 2
0.9 x 2
0.90 x 2
Motor/Drive
Brushless Digitally Controlled / Direct
Operating Range (RPM)
Cooling
0 - 1,150
0 - 1,150
0 - 1,150
0 - 1,150
Heating
80 - 1,150
80 - 1,150
80 - 1,150
80 - 1,150
Maximum Air Volume (CFM)
11,300
11,300
11,300
11,300
Unit Data
Refrigerant Type
R410A
R410A
R410A
R410A
Refrigerant Control/Location
EEV / Indoor Unit
EEV / Indoor Unit
EEV / Indoor Unit
EEV / Indoor Unit
Factory Charge lbs. of R410A
26.5
30.9
37.5
37.5
Max. No. Indoor Units/System
3
29
32
35
39
Sound Pressure dB(A)
4
61.0
62.0
64.0
65.0
Net Unit Weight (lbs.)
639
659
666
666
Shipping Weight (lbs.)
666
688
694
694
Communication Cables
5,6
2 x 18
2 x 18
2 x 18
2 x 18
Heat Exchanger
Material and Fin Coating
Copper Tube / Aluminum Fin and Black Coated Fin™ / Hydrophilic
Rows / Fins per inch
3 / 17
3 / 17
3 / 17
3 / 17
Piping for Heat Recovery Operation
7
Liquid Line Connection (in., OD)
5/8 Braze
5/8 Braze
5/8 Braze
5/8 Braze
Low Pressure Vapor Line Connection (in., OD)
1-1/8 Braze
1-1/8 Braze
1-1/8 Braze
1-3/8 Braze
High Pressure Vapor Line Connection (in., OD)
7/8 Braze
1-1/8 Braze
1-1/8 Braze
1-1/8 Braze
Piping for Heat Pump Operation
7
Liquid Line Connection (in., OD)
5/8 Braze
5/8 Braze
5/8 Braze
5/8 Braze
Vapor Line Connection (in., OD)
1-1/8 Braze
1-1/8 Braze
1-1/8 Braze
1-3/8 Braze
1
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level
with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and
indoor units. All capacities are net with a Combination Ratio between 95–105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb
(DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and
75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb
(DB) and 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and
43ºF wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
The System Combination Ratio must be between 50–130%.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5
Communication cable between Master ODU to Slave ODU(s), and Master ODU to IDUs /
HRUs to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication
cable shield is properly grounded to the Master ODU chassis only. Do not ground the
ODU to IDUs / HRUs communication cable at any other point. Wiring must comply with all
applicable local and national codes.
6
Power wiring is field provided, solid or stranded, and must comply with the applicable
local and national codes. See page 19 for detailed electrical data.
7
LG requires that LATS software be used on all projects to ensure correct line sizing.
Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only.