Refrigerant Piping System Installation for Heat Recovery Operation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Heat Recovery System Piping / Sample Layouts
INSTALLING FOR HEAT RECOVERY
OPERATION
Combining Heat Recovery Ports for Large Indoor Units
It is necessary to combine two ports on a heat recovery unit when installing a single indoor unit with a capacity exceeding 54,000 Btu/h. Two
neighboring heat recovery ports are combined using a reverse Y-branch that is then connected to the one large indoor unit.
First Heat Recovery Unit
Second Heat Recovery Unit
1
2 3
4
96
Mbh
1
2 3
4
28
Mbh
28
Mbh
Top
Top
21
Mbh
76
Mbh
7
Mbh
Heat Recovery Unit Ports Connections for Large Indoor Units.
If large capacity indoor units (larger than 54,000 Btu/h) are installed, the Y-branch pipe shown in the table below must be used to twin the ports.
Kit Model
No.
Vapor Pipe Dimensions
Liquid Pipe Dimensions
Unit: Inch
ARBLN03321
16-1/4
15-3/8
I.D. 3/4
I.D. 3/4
I.D. 3/4
I.D. 1/2
I.D. 1/2
2-3/4
I.D. 5/8
I.D. 5/8
I.D. 1
I.D. 1
O.D. 1
3-3/16
4-3/8
3-5/16
2
3
3
O.D. 3/4
O.D. 3/4
1
2
I.D. 7/8
I.D. 7/8
I.D. 7/8
I.D. 1-1/8
1
I.D. 1/2
I.D. 1/2
I.D. 1/2
13-1/16
12-5/8
I.D. 1/4
I.D. 1/4
I.D. 3/8
I.D. 3/8
I.D. 3/8
2-15/16
Vapor Pipe
Model No.
Liquid Pipe
Model No.
AJR54072902
AJR54072906
Heat Recovery System
Piping
Heat recovery systems have three pipes (liquid,
high pressure vapor, low pressure vapor) running
from the outdoor unit to the heat recovery unit,
then two pipes (liquid, vapor) running from the heat
recovery unit to the connected indoor units.
Vapor Pipe
Vapor Pipe
Liquid Pipe
Liquid Pipe
Heat Recovery Unit
High
Pressure
Vapor Pipe
Liquid Pipe
Low Pressure
Vapor Pipe
1 2
3 4
Simplified Diagram of Heat Recovery System Piping.