TI V 5 Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 10: Triple Frame 460V Outdoor Units.
460V Outdoor Units
SPECIFICATIONS
Combination Unit Model Number
ARUM432DTE5
36.0 Ton
ARUM456DTE5
38.0 Ton
ARUM480DTE5
40.0 Ton
ARUM504DTE5
42.0 Ton
Individual Component Model Numbers
ARUM1
ARUM1
ARUM192DTE5
ARUM1
ARUM1
ARUM216DTE5
ARUM1
ARUM1
ARUM216DTE5
ARUM1
ARUM1
ARUM216DTE5
Cooling Performance
Nominal Cooling Capacity (Btu/h)
1
432,000
456,000
480,000
504,000
Rated Cooling Capacity (Btu/h)
2
412,000
434,000
458,000
480,000
Heating Performance
Nominal Heating Capacity (Btu/h)
1
486,000
513,000
540,000
567,000
Rated Heating Capacity (Btu/h)
2
460,000
488,000
513,000
539,000
Operating Range
Cooling (°F DB)
5 to 122
5 to 122
5 to 122
5 to 122
Heating (°F WB)
-13 to +61
-13 to +61
-13 to +61
-13 to +61
Synchronous — Cooling Based (°F DB)
14 to 81
14 to 81
14 to 81
14 to 81
Synchronous — Heating Based (°F WB)
14 to 61
14 to 61
14 to 61
14 to 61
Compressor
Inverter Quantity
HSS DC Scroll x 4
HSS DC Scroll x 4
HSS DC Scroll x 5
HSS DC Scroll x 5
Oil/Type
PVE / FVC68D
PVE / FVC68D
PVE / FVC68D
PVE / FVC68D
Fan (Top Discharge)
Type
Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
Motor Output (kW) x Qty.
0.90x2 + 0.90x2 + 0.90x2 0.90x2 + 0.90x2 + 0.90x2 0.90x2 + 0.90x2 + 0.90x2 0.90x2 + 0.90x2 + 0.90x2
Motor/Drive
Brushless Digitally Controlled / Direct
Operating Range (RPM)
Cooling
0 - 1,150
0 - 1,150
0 - 1,150
0 - 1,150
Heating
80 - 1,150
80 - 1,150
80 - 1,150
80 - 1,150
Maximum Air Volume (CFM)
33,900
33,900
33,900
33,900
Unit Data
Refrigerant Type
R410A
R410A
R410A
R410A
Refrigerant Control/Location
EEV / Indoor Unit
EEV / Indoor Unit
EEV / Indoor Unit
EEV / Indoor Unit
Factory Charge lbs. of R410A
23.2 + 23.2 + 30.9
23.2 + 23.2 + 37.5
23.2 + 26.5 + 37.5
23.2 + 26.5 + 37.5
Max. No. Indoor Units/System
3
64
64
64
64
Sound Pressure dB(A)
4
66.0
66.0
67.0
67.0
Net Unit Weight (lbs.)
507 + 507 + 659
507 + 507 + 666
507 + 639 + 666
507 + 639 + 666
Shipping Weight (lbs.)
534 + 534 + 688
534 + 534 + 694
534 + 666 + 694
534 + 666 + 694
Communication Cables
5,6
2 x 18
2 x 18
2 x 18
2 x 18
Heat Exchanger
Material and Fin Coating
Copper Tube / Aluminum Fin and Black Coated Fin™ / Hydrophilic
Rows / Fins per inch
2/17 x 2 + 3/17
2 / 17 x 2 + 3 / 17
2 / 17 + 3 / 17 x 2
2 / 17 + 3 / 17 x 2
Piping for Heat Recovery Operation
7
Liquid Line Connection (in., OD)
1/2 & 1/2 & 5/8 Braze
1/2 & 1/2 & 5/8 Braze
1/2 & 1/2 & 5/8 Braze
1/2 & 5/8 & 5/8 Braze
Low Pressure Vapor Line Conn. (in., OD) 1-1/8 & 1-1/8 & 1-1/8 Braze 1-1/8 & 1-1/8 & 1-1/8 Braze 1-1/8 & 1-1/8 & 1-1/8 Braze 1-1/8 & 1-1/8 & 1-1/8 Braze
High Pressure Vapor Line Conn. (in., OD) 3/4 & 3/4 & 1-1/8 Braze 3/4 & 3/4 & 1-1/8 Braze 3/4 & 7/8 & 1-1/8 Braze 3/4 & 7/8 & 1-1/8 Braze
Piping for Heat Pump Operation
7
Liquid Line Connection (in., OD)
1/2 & 1/2 & 5/8 Braze
1/2 & 1/2 & 5/8 Braze
1/2 & 1/2 & 5/8 Braze
1/2 & 5/8 & 5/8 Braze
Vapor Line Connection (in., OD)
1-1/8 & 1-1/8 & 1-1/8 Braze 1-1/8 & 1-1/8 & 1-1/8 Braze 1-1/8 & 1-1/8 & 1-1/8 Braze 1-1/8 & 1-1/8 & 1-1/8 Braze
1
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level
with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and
indoor units. All capacities are net with a Combination Ratio between 95–105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb
(DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and
75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb
(DB) and 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and
43ºF wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
The System Combination Ratio must be between 50–130%.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5
Communication cable between Master ODU to Slave ODU(s), and Master ODU to IDUs /
HRUs to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication
cable shield is properly grounded to the Master ODU chassis only. Do not ground the
ODU to IDUs / HRUs communication cable at any other point. Wiring must comply with all
applicable local and national codes.
6
Power wiring is field provided, solid or stranded, and must comply with the applicable
local and national codes. See page 20 for detailed electrical data.
7
LG requires that LATS software be used on all projects to ensure correct line sizing.
Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only.