TI V 5 Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Error Code
Description
Details
Heat Recovery Unit
- 5 1
C +
No.
of HR
Unit
Capacity of indoor units connected to the heat
recovery unit exceeds allowable limits.
The amount of nominal cooling capacity of indoor units con-
nected to a heat recovery unit, or a heat recovery unit port, or
capacity of grouped heat recovery unit port is excessive. After
auto-pipe detection is complete, wait 5 minutes, then verify
connected capacity. System will display error if:
• The heat recovery unit port addresses are all unique, but >54
Mbh single indoor unit connected; >54 Mbh total of multiple
indoor units connected.
• If 2 heat recovery unit port addresses are the same and the
ports are twinned; >108 Mbh total of multiple indoor units are
connected.
• If 3 heat recovery unit port addresses are the same and the
ports are all connected, or >162 Mbh total of multiple indoor
units connected.
• If the total connected indoor unit nominal capacity exceeds
192 Mbh for a single heat recovery unit.
• Error code displays on the outdoor unit SSD, the heat recov-
ery unit SSD, or in LGMV.
2 0 0
1 Auto pipe search failure.
Auto piping procedure did not complete properly.
2 0 1
C +
No.
of HR
Unit
Heat recovery unit liquid sensor error. (C = Heat
recovery unit + Heat recovery unit
number).
Disconnection or short circuit of heat recovery unit liquid pipe
sensor.
2 0 2
Heat recovery unit subcooling pipe inlet sensor
error. (C = Heat recovery unit + Heat recovery unit
number).
Disconnection or short circuit of heat recovery unit subcooling
pipe inlet sensor.
2 0 3
Heat recovery unit subcooling pipe outlet sensor
error. (C = Heat recovery unit + Heat recovery unit
number).
Disconnection or short circuit of heat recovery unit subcooling
pipe outlet sensor.
2 0 4
Communication error between outdoor unit and
heat recovery unit. (C = Heat recovery unit + Heat
recovery unit number)
Outdoor unit does not receive signal from heat recovery unit.
2 0 5
Communication error between heat recovery unit
(2A Series) and the 485 modem. The 2A Series heat
recovery unit applies only to heat recovery systems
communicating at a baud rate of 9,600 bps.
• The 485 modem is the communications style on
the bus that is 1e outdoor unit to many indoor units.
• Communication problem occurred between the heat recovery
unit PCB and the connection to the communications bus.
• Error displays if the outdoor unit signal is not received for
three (3) minutes. The error clears after the signal is received
from the modem. (2A Series Heat Recovery Units.)
2 0 6
Duplicate address error of the heat recovery unit
(2A Series).
• The 2A Series heat recovery unit applies only to
heat recovery systems communicating at a baud
rate of 9,600 bps.
• The 485 modem is the communications style on the
bus that is 1e outdoor unit to many indoor units.
• A heat recovery unit address is duplicated for 485 communi-
cation.
• There are two heat recovery units with one or more HEX
addresses that are the same.
• Adjust the hex address dial found on the heat recovery units.
Network
2 4 2
* Network error of central controller.
Inability of the central controller to receive information from the
outdoor unit.
For detailed information on how to troubleshoot each error, see the Multi V Service Manual on www.lghvac.com.
ERROR CODE TABLES