165
Error Codes
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Error Code
Description
Details
Outdoor Unit
7
7
1 Master outdoor unit fan overcurrent error.
Outdoor unit fan current is >10A (for 208-230V units) or 5A (for
460V units).
7
7
2 Slave1 outdoor unit fan overcurrent error.
Slave1 outdoor unit fan current is >10A (for 208-230V units) or
5A (for 460V units).
7
7
3 Slave2 outdoor unit fan overcurrent error.
Slave2 outdoor unit fan current is >10A (for 208-230V units) or
5A (for 460V units).
7
9
1 Master outdoor unit fan operation failure error.
Master outdoor unit fan is experiencing first position sensor
failure.
7
9
2 Slave1 outdoor unit fan operation failure error.
Slave1 outdoor unit fan is experiencing first position sensor
failure.
7
9
3 Slave2 outdoor unit fan operation failure error.
Slave2 outdoor unit fan is experiencing first position sensor
failure.
8
6
1 Master outdoor unit main PCB onboard EPROM error. • Verify the EPROM is present and in the socket correctly.
• Check if all pins are in and are not bent.
• Check if notch in the chip lines up with the arrow on the
socket.
8
6
2 Slave1 outdoor unit main PCB onboard EPROM error.
8
6
3 Slave2 outdoor unit main PCB onboard EPROM error.
8
7
1 Master outdoor unit fan PCB EPROM error.
• Communication error between master outdoor unit fan MICOM
and EPROM.
• Verify EPROM is present and in the socket correctly.
8
7
2 Slave1 outdoor unit fan PCB EPROM error.
• Communication error between slave1 outdoor unit fan MICOM
and EPROM.
• Verify EPROM is present and in the socket correctly.
8
7
3 Slave2 outdoor unit fan PCB EPROM error.
• Communication error between slave2 outdoor unit fan MICOM
and EPROM.
• Verify EPROM is present and in the socket correctly.
1 0 4 1 Communication error between master outdoor unit and
slave outdoor units.
Master outdoor unit main PCB is not receiving signals from
slave outdoor units.
1 0 4 2 Communication error between slave1 outdoor unit and
master and slave2 outdoor units.
Slave1 outdoor unit main PCB is not receiving signals from
master and slave2 outdoor units.
1 0 4 3 Communication error between slave2 outdoor unit and
master and slave1 outdoor units.
Slave2 outdoor unit main PCB is not receiving signals from
master and slave1 outdoor units.
1 0 5 1 Master outdoor unit fan PCB communication error.
Master outdoor unit main PCB is not receiving a signal from the
fan.
1 0 5 2 Slave1 outdoor unit fan PCB communication error.
Slave1 outdoor unit main PCB is not receiving a signal from the
fan.
1 0 5 3 Slave2 outdoor unit fan PCB communication error.
Slave2 outdoor unit main PCB is not receiving a signal from the
fan.
1 0 6 1 Master outdoor unit fan IPM error.
Instant overcurrent (peak) of master outdoor unit fan IPM.
1 0 6 2 Slave1 outdoor unit fan IPM error.
Instant overcurrent (peak) of slave1 outdoor unit fan IPM.
1 0 6 3 Slave2 outdoor unit fan IPM error.
Instant overcurrent (peak) of slave2 outdoor unit fan IPM.
1 0 7 1 Master outdoor unit fan DC link low voltage error.
A capacitor that is serving the ODU fan inverter is not working
properly, or the voltage at the capacitor is out of range (low).
• Outdoor unit fan DC link voltage is <50V for a minimum of
250µs (for both 208-230V and 460V units).
• Disconnected DC link.
• Damaged electrical condenser component (serving capacitor)
on inverter driver board.
1 0 7 2 Slave1 outdoor unit fan DC link low voltage error.
1 0 7 3 Slave2 outdoor unit fan DC link low voltage error.
Table 78: Error Codes, continued.
For detailed information on how to troubleshoot each error, see the Multi V Service Manual on www.lghvac.com.
ERROR CODE TABLES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING