Error Code
Description
Details
Outdoor Unit
5 2 1 Communication error between master outdoor unit main
PCB and inverter PCB.
• Communication error between main PCB (CN-29) and inverter
PCB CN-MAIN (COM/RD).
• Check connections at both sockets.
• Inspect interconnecting cable for wear.
5 2 2 Communication error between slave1 outdoor unit main
PCB and inverter PCB.
5 2 3 Communication error between slave2 outdoor unit main
PCB and inverter PCB.
5 3 1 Communication error between outdoor unit main PCB
and indoor unit(s) PCB.
• Check if outdoor unit to indoor unit(s) communications cable
disconnected or shorted.
• Check A terminals are connected to indoor unit A(3) (5 on 3 x
3 cassette) terminals; B(4) (6 on 3 x 3 cassette) terminals.
5 7 1 Master outdoor unit main PCB and inverter PCB
communication error.
Master outdoor unit inverter PCB is not receiving signal from
main PCB.
5 7 2 Slave1 outdoor unit main PCB and inverter PCB
communication error.
Slave1 outdoor unit inverter PCB is not receiving signal from
main PCB.
5 7 3 Slave2 outdoor unit main PCB and inverter PCB
communication error.
Slave2 outdoor unit inverter PCB is not receiving signal from
main PCB.
6 0 1 Master outdoor unit inverter PCB EPROM error.
• Verify the EPROM is present and in the socket correctly.
• Check if all pins are in and are not bent.
• Check if notch in the chip lines up with the arrow on the
socket.
6 0 2 Slave1 outdoor unit inverter PCB EPROM error.
6 0 3 Slave2 outdoor unit inverter PCB EPROM error.
6 2 1 High temperature at the master outdoor unit inverter
heatsink.
System shut off because of high temperatures at the master
outdoor unit inverter heatsink.
6 2 2 High temperature at the slave1 outdoor unit inverter
heatsink.
System shut off because of high temperatures at the slave1
outdoor unit inverter heatsink.
6 2 3 High temperature at the slave2 outdoor unit inverter
heatsink.
System shut off because of high temperatures at the slave2
outdoor unit inverter heatsink.
6 5 1 Master outdoor unit inverter heatsink temperature
sensor error.
Master outdoor unit inverter heatsink temperature sensor dis-
connected or shorted.
6 5 2 Slave1 outdoor unit inverter heatsink temperature
sensor error.
Slave1 outdoor unit inverter heatsink temperature sensor dis-
connected or shorted.
6 5 3 Slave2 outdoor unit inverter heatsink temperature
sensor error.
Slave2 outdoor unit inverter heatsink temperature sensor dis-
connected or shorted.
6 7 1 Master outdoor unit fan has locked up.
No airflow.
6 7 2 Slave1 outdoor unit fan has locked up.
6 7 3 Slave2 outdoor unit fan has locked up
7 1 1 Master outdoor unit inverter CT sensor error.
Master outdoor unit is restricted.
7 1 2 Slave1 outdoor unit inverter CT sensor error.
Slave1 outdoor unit is restricted.
7 1 3 Slave2 outdoor unit inverter CT sensor error.
Slave2 outdoor unit is restricted.
7 5 1 Master outdoor unit fan CT sensor error.
Master outdoor unit fan current detection (CT) sensor discon-
nected or shorted.
7 5 2 Slave1 outdoor unit fan CT sensor error.
Slave1 outdoor unit fan current detection (CT) sensor discon-
nected or shorted.
7 5 3 Slave2 outdoor unit fan CT sensor error.
Slave2 outdoor unit fan current detection (CT) sensor discon-
nected or shorted.
Table 77: Error Codes, continued.
ERROR CODE TABLES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
For detailed information on how to troubleshoot each error, see the Multi V Service Manual on www.lghvac.com.