Error Codes
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Error Code
Description
Details
1 5 3 1 Master outdoor unit upper heat exchanger temperature
sensor error.
• Check the connection on the outdoor unit PCB.
• Thermistor is disconnected or shorted.
1 5 3 2 Slave1 outdoor unit upper heat exchanger temperature
sensor error.
1 5 3 3 Slave2 outdoor unit upper heat exchanger temperature
sensor error.
1 5 4 1 Master outdoor unit lower heat exchanger temperature
sensor error.
• Check the connection on the outdoor unit PCB.
• Thermistor disconnected or shorted.
1 5 4 2 Slave1 outdoor unit lower heat exchanger temperature
sensor error.
1 5 4 3 Slave2 outdoor unit lower heat exchanger temperature
sensor error.
1 8 2 1 Communication error between master outdoor unit
external board main and sub MICOMs.
Master outdoor unit external board main to sub MICOMs
communication failure.
1 8 2 2 Communication error between slave1 outdoor unit
external board main and sub MICOMs.
Slave1 outdoor unit external board main to sub MICOMs
communication failure.
1 8 2 3 Communication error between slave2 outdoor unit
external board main and sub MICOMs.
Slave2 outdoor unit external board main to sub MICOMs
communication failure.
1 8 7 1 Hydro kit P, HEX error (P equals prevents from freez-
ing).
• Water outlet temperature sensor is disconnected or shorted.
Values read less than -43°C or greater than +96°C (less than
-45.4°F or greater than +204.8°F).
• Prevents HEX from bursting when operating. Does not protect
HEX if the glycol is inadequate, nor if the hydro kit is off and
not operating.
Outdoor unit compressor ramps up, and hydro kit operates. One
(1) minute later, pipe temperature at mid-temperature hot water
supply (inlet or outlet water) is <0°C (32°F), and mid-tempera-
ture hot water supply (inlet or outlet water) is ≤4°C (39.2°F) for
ten (10) seconds.
1 9 3 1 Excessive increase in master outdoor unit fan heatsink
temperature.
System has shut off because master outdoor unit fan heatsink
temperature is >203°F.
1 9 3 2 Excessive increase in slave1 outdoor unit fan heatsink
temperature.
System has shut off because slave1 outdoor unit fan heatsink
temperature is >203°F.
1 9 3 3 Excessive increase in slave2 outdoor unit fan heatsink
temperature.
System has shut off because slave1 outdoor unit fan heatsink
temperature is >203°F.
1 9 4 1 Master outdoor unit fan heatsink temperature
sensor error.
Disconnection or short circuit of master outdoor unit fan heat-
sink temperature sensor.
1 9 4 2 Slave1 outdoor unit fan heatsink temperature
sensor error.
Disconnection or short circuit of slave1 outdoor unit fan heatsink
temperature sensor.
1 9 4 3 Slave2 outdoor unit fan heatsink temperature
sensor error.
Disconnection or short circuit of slave2 outdoor unit fan heatsink
temperature sensor.
ERROR CODE TABLES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
Table 80: Error Codes, continued.
For detailed information on how to troubleshoot each error, see the Multi V Service Manual on www.lghvac.com.