Systems designed for heat recovery operation can use also Y-branches and Headers in combination with heat recovery units.
Indoor Unit
48,000 Btu/h
Indoor Unit
48,000 Btu/h
Indoor Unit
48,000 Btu/h
Indoor Unit
48,000 Btu/h
Heat Recovery Unit 1
Heat Recovery Unit 2
Maximum total Indoor Unit capacity is 192,000 Btu/h.
Indoor Unit
48,000 Btu/h
Indoor Unit
48,000 Btu/h
Indoor Unit
48,000 Btu/h
Indoor Unit
48,000 Btu/h
Heat Recovery Unit
Outdoor Unit
Header
Indoor Unit
12,000 Btu/h
Indoor Unit
12,000 Btu/h
Indoor Unit
12,000 Btu/h
Indoor Unit
12,000 Btu/h
Outdoor Unit
Heat Recovery Unit
Maximum total Indoor Unit capacity per Heat Recovery Unit branch pipe is 54,000 Btu/h.
Outdoor Unit
Heat Recovery Unit
Outdoor Unit
Header
Indoor Unit
24,000 Btu/h
Indoor Unit
24,000 Btu/h
Y-Branch
Y-Branch
Y-Branch
Indoor Unit
12,000 Btu/h
Indoor Unit
12,000 Btu/h
Indoor Unit
12,000 Btu/h
Y-Branch
Sample Layouts
INSTALLING FOR HEAT RECOVERY
OPERATION
Images are for illustrative purposes only and are not accurate representations. For specific details on piping limitations and other refrigerant system
rules, review the information in this entire piping section, see the Multi V 5 Engineering Manual, and follow the LATS diagram.