Error Code
Description
Details
1 0
- Indoor unit BLDC fan motor communications error.
• Fan motor has been removed or is defective. Refer to the resis-
tance and voltage check charts in the product service manual.
• The system has detected the fan motor is not spinning.
• On new installs, verify installation manual and paperwork were
removed from fan discharge shroud during installation.
• Check the wiring plug and connections (if applicable).
1 1
- Communication error between hydro kit and inverter
compressor PCB.
Hydro kit is not receiving communications signal from inverter
compressor PCB.
1 2
- Hydro kit inverter compressor PCB error.
Hydro kit inverter compressor PCB error.
1 3
- Hydro kit solar heat pipe temperature sensor error.
Solar heat pipe temperature sensor disconnected or shorted.
1 4
- Hydro kit flow switch error.
Flow switch failed to close.
1 5
- Hydro Kit leaving water temperature has exceeded
185°F (85°C).
Temperature sensor is defective or there is hot water inflow.
1 6
- Hydro kit indoor unit water pipe temperature and ambi-
ent temperature sensor communication error.
Water inlet and outlet pipe temperature sensor disconnected or
shorted.
1 7
-
Hydro kit inlet pipe temperature sensor communication
error.
Outside air duct inlet pipe temperature sensor commu-
nication error.
• Water inlet temperature sensor disconnected or shorted. Values
read less than -43°C or greater than +96°C (less than -45.4°F
or greater than +204.8°F).
• Temperature sensor disconnected or shorted.
1 8
- Hydro kit outlet pipe temperature sensor communica-
tion error.
Outlet pipe temperature sensor disconnected or short circuited.
2 3 0 Refrigerant leak sensor error.
• Refrigerant leak sensor error; sensor is malfunctioning.
• Refrigerant leak is detected when >6,000 ppm.
• Enable the function through the function code on the remote
controller.
1. Operation stop.
2. Solenoid valve closes on the indoor unit side.
3. CH230 is displayed. If the communication baud is 1,200 bps,
then only the zone controller can display the CH230; central
controller cannot display the error due to lack of information.
4. Buzzer rings 2 long buzzes every 1 second. Ringing stops
when there is an input from the controller. (If there is a hard
lock, then only the controller can make the hard lock to stop
buzzing. If leak sensor measures under 1.5V, then it is consid-
ered normal and the buzzing stops.
5. To release the error, power needs reset.
2 3 7 Communication error between indoor unit communica-
tions PCB and outdoor unit PCB.
Indoor unit communications PCB is not receiving signal from out-
door unit communication PCB for >3 consecutive minutes. Check
PCBs for issues.
2 3 8 Communication error between outdoor unit communi-
cations PCB and outdoor unit.
Outdoor unit communications PCB is not receiving signal from
outdoor unit for >3 consecutive minutes. Check PCB for issues.
Table 73: Error Codes, continued.
For detailed information on how to troubleshoot each error, see the Multi V Service Manual on www.lghvac.com.
ERROR CODE TABLES
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING