Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 3: Dual Frame 208-230V Outdoor Units.
SPECIFICATIONS
208-230V Outdoor Units
Unit Model Number
ARUM264BTE5
22.0 Ton
ARUM288BTE5
24.0 Ton
ARUM312BTE5
26.0 Ton
ARUM336BTE5
28.0 Ton
Individual Component Model Numbers
ARUM0
ARUM168BTE5
ARUM0
ARUM192BTE5
ARUM0
ARUM216BTE5
ARUM1
ARUM216BTE5
Cooling Performance
Nominal Cooling Capacity (Btu/h)
1
264,000
288,000
312,000
336,000
Rated Cooling Capacity (Btu/h)
2
252,000
276,000
298,000
320,000
Heating Performance
Nominal Heating Capacity (Btu/h)
1
297,000
324,000
351,000
378,000
Rated Heating Capacity (Btu/h)
2
283,000
309,000
333,000
359,000
Operating Range
Cooling (°F DB)
5 to 122
5 to 122
5 to 122
5 to 122
Heating (°F WB)
-13 to +61
-13 to +61
-13 to +61
-13 to +61
Synchronous — Cooling Based (°F DB)
14 to 81
14 to 81
14 to 81
14 to 81
Synchronous — Heating Based (°F WB)
14 to 61
14 to 61
14 to 61
14 to 61
Compressor
Inverter Quantity
HSS DC Scroll x 3
HSS DC Scroll x 3
HSS DC Scroll x 3
HSS DC Scroll x 3
Oil/Type
PVE / FVC68D
PVE / FVC68D
PVE / FVC68D
PVE / FVC68D
Fan (Top Discharge)
Type
Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
Motor Output (kW) x Qty.
0.90 x 2 + 0.90 x 2
0.90 x 2 + 0.90 x 2
0.90 x 2 + 0.90 x 2
0.90 x 2 + 0.90 x 2
Motor/Drive
Brushless Digitally Controlled / Direct
Operating Range (RPM)
Cooling
0 - 1,150
0 - 1,150
0 - 1,150
0 - 1,150
Heating
80 - 1,150
80 - 1,150
80 - 1,150
80 - 1,150
Maximum Air Volume (CFM)
22,600
22,600
22,600
22,600
Unit Data
Refrigerant Type
R410A
R410A
R410A
R410A
Refrigerant Control/Location
EEV / Indoor Unit
EEV / Indoor Unit
EEV / Indoor Unit
EEV / Indoor Unit
Factory Charge lbs. of R410A
23.2 + 26.5
23.2 + 30.9
23.2 + 37.5
23.2 + 37.5
Max. No. Indoor Units/System
3
42
45
52
55
Sound Pressure dB(A)
4
63.0
63.0
65.0
65.0
Net Unit Weight (lbs.)
507 + 639
507 + 659
507 + 666
507 + 666
Shipping Weight (lbs.)
534 + 666
534 + 688
534 + 694
534 + 694
Communication Cables
5,6
2 x 18
2 x 18
2 x 18
2 x 18
Heat Exchanger
Material and Fin Coating
Copper Tube / Aluminum Fin and Black Coated Fin™ / Hydrophilic
Rows / Fins per inch
2 / 17 + 3 / 17
2 / 17 + 3 / 17
2 / 17 + 3 / 17
2 / 17 + 3 / 17
Piping for Heat Recovery Operation
7
Liquid Line Connection (in., OD)
3/8 & 5/8 Braze
3/8 & 5/8 Braze
3/8 & 5/8 Braze
1/2 & 5/8 Braze
Low Pressure Vapor Line Connection (in., OD)
7/8 & 1-1/8 Braze
7/8 & 1-1/8 Braze
7/8 & 1-1/8 Braze
1-1/8 & 1-1/8 Braze
High Pressure Vapor Line Connection (in., OD)
3/4 & 7/8 Braze
3/4 & 1-1/8 Braze
3/4 & 1-1/8 Braze
3/4 & 1-1/8 Braze
Piping for Heat Pump Operation
7
Liquid Line Connection (in., OD)
3/8 & 5/8 Braze
3/8 & 5/8 Braze
3/8 & 5/8 Braze
1/2 & 5/8 Braze
Vapor Line Connection (in., OD)
7/8 & 1-1/8 Braze
7/8 & 1-1/8 Braze
7/8 & 1-1/8 Braze
1-1/8 & 1-1/8 Braze
1
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level
with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and
indoor units. All capacities are net with a Combination Ratio between 95–105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb
(DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and
75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb
(DB) and 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and
43ºF wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
The System Combination Ratio must be between 50–130%.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5
Communication cable between Master ODU to Slave ODU(s), and Master ODU to IDUs /
HRUs to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication
cable shield is properly grounded to the Master ODU chassis only. Do not ground the
ODU to IDUs / HRUs communication cable at any other point. Wiring must comply with all
applicable local and national codes.
6
Power wiring is field provided, solid or stranded, and must comply with the applicable
local and national codes. See page 19 for detailed electrical data.
7
LG requires that LATS software be used on all projects to ensure correct line sizing.
Designer must verify the shop drawing design against the as built design using LATS.
Contractor must also use LG manufactured Y-Branch and Header Kits only.