156
MUL
TI V 5 Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Model
Capacity
(MBh)
Mode
Setting Value
Standard ESP (in.
wg)
CFM
Min. ESP (in.
wg)
Max. ESP (in.
wg)
ARNU483BRA4
48.1
High
(Factory Set)
High
116
0.55
1,582
0.39
0.78
Mid
111
1,434
Low
106
1,176
Standard
High
106
0.39
1,568
0.27
0.55
Mid
102
1,395
Low
95
1,183
Table 71: Example of BR Unit External Static Pressure and Air Flow (with Settings) from Ducted Indoor Unit Engineering Manual.
Setting External Static Pressure
PRE-COMMISSIONING
Determining External Static Pressure and Setting the Values
1. For ducted indoor units, the Engineering Manual includes tables listing setting values as they relate to ESP and airflow. The installer can
use the available range of ESP settings to adjust for ductwork in the system. See table below for an example.
The indoor unit fan(s) cannot be allowed to operate outside manufacturer’s parameters. Extended operation in these conditions will result in
•
Fan surge (noisy & slow pulsating airflow), and / or
• Fan motor failure
Set Value
Static Pressure (in. wg)
0.19
0.23
0.31
0.39
0.47
0.55
0.59
0.62
0.66
0.70
0.78
91
1,642
1,543
1,349
1,105
819
494
317
130
-
-
-
96
1,762
1,628
1,518
1,183
1,098
649
483
317
91
-
-
101
1,839
1,772
1,691
1,395
1,320
964
889
628
314
215
-
106
1,815
1,808
1,779
1,568
1,522
1,176
1,133
1,020
741
632
293
111
1,892
1,896
1,868
1,762
1,705
1,433
1,419
1,158
1,112
960
618
116
-
-
-
1,967
1,794
1,582
1,504
1,416
1,327
1,147
974
121
-
-
-
-
1,843
1,794
1,776
1,613
1,575
1,370
1,137
126
-
-
-
-
-
-
1,921
1,808
1,779
1,624
1,536
Table 72: BR Unit External Static Pressure and Air Flow Table from Ducted Indoor Unit Engineering Manual.
Fan RPM = fan setting value x 10.
2. The table below presents the ESP settings that the unit comes with from the factory, plus an additional “standard” setting.
3. Once the available system static pressure requirements and the desired airflow rate are known, select the required ESP (fan) setting
value(s). A separate ESP (fan) setting value should be selected for each available indoor unit fan speed.
4. Record the values on the Pre-Commissioning Device Configuration Worksheet. If the fan setting value was left at the factory default,
insert “000” in the blank.