Complete the following steps until the problem is solved:
1. Make sure that you are using the correct password and that the capitals lock is off.
2. Contact Support for further assistance if you have forgotten the password.
Cannot ping the CMM on the management network
Use the information in this section to troubleshoot the compute node when one or more compute nodes
cannot ping the CMM on the management network.
Single node cannot ping the CMM in the same chassis
Use the information in this section to troubleshoot a single compute node that cannot ping the CMM on the
management network in the same chassis.
Complete the following steps until the problem is solved:
1. Make sure that the Chassis Management Module is powered on and the applicable ports are enabled on
the CMM.
2. Make sure that the compute node IMM has acquired an IP address from the CMM by using the Setup
utility on the node.
Note:
If the CMM recently lost connection to the DCHP server, you must reset the IMM by using the
CMM interface so that a new IP address can be acquired.
3. In the CMM user interface, click
Chassis Management > Component IP Configuration
and make
sure that the IP address that is listed is the same as the IP address that is displayed in the Setup
utility. If it is not the same IP address, configure the IMM network settings correctly or reset the IMM to
automatically acquire a new IP address.
4. Check http://www.lenovo.com/support for any firmware updates that might apply to this problem. You
can view the release notes for a firmware update to determine the issues that the update addresses.
5. Remove the compute node from the chassis and check the connectors on the back of the node for
bent pins. If the pins are bent, contact Support.
6. Install the compute node in another node bay to determine whether the problem remains. If the problem
remains, make sure that the compute node is connected to a port that has been enabled and that the
vLAN settings allow that port to connect to the network.
7. Check http://www.lenovo.com/support for any service bulletins that are related to network connectivity.
8. (Trained service technician only) Complete the following steps:
a. Force the link/duplex speed.
b. Check the connectors on the I/O module to make sure that no pins are bent.
c. Check the connectors on the chassis midplane to make sure that no pins are bent.
d. Remove the CMM and install a working CMM in the same bay.
e. If the problem is solved, replace the CMM that you removed.
Multiple nodes cannot ping the CMM in the same chassis
Use the information in this section to troubleshoot multiple nodes that cannot ping the CMM on the
management network in the same chassis.
Complete the following steps until the problem is solved:
1. Make sure that the Chassis Management Module is powered on and the applicable ports are enabled on
the CMM. If the CMM is hung, reset the CMM.
2. Reset the CMM.
3. Check for firmware updates for the CMM.
619
Содержание Flex System x220
Страница 1: ...Flex System x220 Compute Node Installation and Service Guide Machine Types 7906 2585 ...
Страница 50: ...42 Flex System x220 Compute Node Installation and Service Guide ...
Страница 54: ...46 Flex System x220 Compute Node Installation and Service Guide ...
Страница 68: ...60 Flex System x220 Compute Node Installation and Service Guide ...
Страница 644: ...636 Flex System x220 Compute Node Installation and Service Guide ...
Страница 698: ...690 Flex System x220 Compute Node Installation and Service Guide ...
Страница 705: ...Taiwan BSMI RoHS declaration Appendix B Notices 697 ...
Страница 706: ...698 Flex System x220 Compute Node Installation and Service Guide ...
Страница 713: ......
Страница 714: ...Part Number 00YJ297 Printed in China 1P P N 00YJ297 1P00YJ297 ...