54
6-2. INPUT SETTING
6-2-1. Smoothing
Smoothing is a function whereby fluctuations of the display values are made stable by eliminating unnecessary noise
component.
Though the most popular noise at the site is a hum noise due to the AC power, noise due to the motor in the control
system also generates frequently.
The smoothing function has analog and digital methods.
(1) Analog Filter
Creates the low-pass filter circuit by using the analog circuit, offers easy-passage to input signal smaller than the
preset frequency and eliminates the input signal over than that.
<Setting Value>
1 Hz, 30 Hz, 300 Hz, and None (1 kHz or more)
<How to operate>
1) Press the
key on the “
Measuring
” window.
2) Press the
key on the “
Setting
” window.
3) Press the
key on the “
Input Setting
” window.
4) Press the
key on the “
Smoothing
” window.
5) After pressing the target key, press the
key to register the
setting value.
Zero Compensation
Additional Value
Original Value
The original value of sensor
is monitored.
A function that automatically
compensates the fine zero-
shift.
The measured value is display-
ed with adding the 'Additional
Value'.
Input Setting
A function that stables the
indicated value by reducing
unnecessary noise.
Smoothing
Return
Measure
Содержание WGA-910A Series
Страница 112: ...108 7 OPERATION TIMING 7 1 CONTROL INPUT HOLD COMMAND RESET COMMAND ZERO COMMAND 7 1 1 Control Input ...
Страница 113: ...109 7 1 2 Block specified 7 1 3 Time specified ...
Страница 114: ...110 7 2 COMPARATOR OUTPUT 7 3 DELAY TIME BETWEEN INPUT AND OUTPUT Delay time between input RS output MAX 30 ms ...
Страница 145: ...141 11 2 DIMENSIONS Unit mm ...
Страница 150: ...146 Kyowa Electronic Instruments Co Ltd 3 5 1 Chofugaoka Chofu Tokyo 182 8520 Japan http www kyowa ei com ...