Message explanations
385585/C
A-63
RIO: On-board voltage error. REF2 (reset required)
Description:
An internal reference voltage identified as REF2 is out of limits.
Possible
consequences:
All affected IO channels are marked with error, and if input, values are frozen to
last valid value until the problem is solved and a manual reset is activated.
Corrective
actions:
Check cabinet power and earth connections. Try to reset the RIO Module. If this
does not help, replace the module.
RIO: On-board voltage error. Vital CPU voltage PWR1 (reset
required)
Description:
An internal vital CPU voltage identified as PWR1 is out of limits.
Possible
consequences:
All affected IO channels are marked with error, and if input, values are frozen to
last valid value until the problem is solved and a manual reset is activated.
Corrective
actions:
Check cabinet power and earth connections. Try to reset the RIO Module. If this
does not help, replace the module.
RIO: On-board voltage error. Vital CPU voltage PWR1 (restart
required)
Description:
An internal vital CPU voltage identified as PWR1 is out of limits, This error is by
application configured to make the RIO module non-operational.
Possible
consequences:
The RIO module is not operational. All output values are zero and input is frozen
until the problem is solved and the module is restarted.
Corrective
actions:
Check cabinet power and earth connections. Try to restart the RIO Module. If this
does not help, replace the module.
RIO: Open loop/Cable break
Description:
A field terminal connection is missing or a field cable is broken (Open loop).
Possible
consequences:
The device connected to the actual channel might not operate as intended. If
signal is input, value is frozen to last valid input as long as alarm is active.
Corrective
actions:
Check physical loop/cabling.
RIO: Overload protection activated (reset required)
Description:
There is probably a short circuit or some external device causing too high current
in the loop.