Message explanations
385585/C
A-57
RIO: Ground monitoring error, upper voltage limit exceeded
Description:
The internal ground monitoring voltage reading for the non-isolated channels is
above the application configured limit.
Possible
consequences:
No immediate functional consequences, but if the condition persists, the signal
values might be affected.
Corrective
actions:
Check if limit is correctly configured. If so, check if any channel related alarms are
active, and check loop/cabling.
RIO: Ground monitoring error, (Iso1) lower voltage limit
exceeded
Description:
The internal ground monitoring voltage reading for the isolated channel 6 is below
the application configured limit.
Possible
consequences:
No immediate functional consequences, but if the condition persists, the signal
values might be affected.
Corrective
actions:
Check if limit is correctly configured. If so, check if any channel related alarms on
1. isolated channel group are active, and check loop/cabling.
RIO: Ground monitoring error, (Iso1) upper voltage limit
exceeded
Description:
The internal ground monitoring voltage reading for the isolated channel 6 is above
the application configured limit.
Possible
consequences:
No immediate functional consequences, but if the condition persists, the signal
values might be affected.
Corrective
actions:
Check if limit is correctly configured. If so, check if any channel related alarms on
1. isolated channel group are active, and check loop/cabling.
RIO: Ground monitoring error, (Iso2) lower voltage limit
exceeded
Description:
The internal ground monitoring voltage reading for the isolated channel 8 is below
the application configured limit.
Possible
consequences:
No immediate functional consequences, but if the condition persists, the signal
values might be affected.
Corrective
actions:
Check if limit is correctly configured. If so, check if any channel related alarms on
2. isolated channel group are active, and check loop/cabling.