Message explanations
385585/C
A-61
Corrective
actions:
Note error data and operational information. Contact Customer Support.
RIO: Not in normal IO mode. Automatically set to normal
Description:
It is detected that the RIO module is in a test or calibration mode. The RBUS
driver will automatically set the module to normal IO mode.
Possible
consequences:
In the short period of time before the mode is forced back to normal, signal values
might be blocked or erroneous.
Corrective
actions:
No action if immediately normalized and not recurrent. Else note error data and
operational information. Contact customer support.
RIO: On-board reference voltage error (reset required)
Description:
Testing of an internally generated voltage has failed.
Possible
consequences:
No immediate consequence for I/O-values, but is a symptom that something is
wrong either with external power/cabling or RIO Module FW.
Corrective
actions:
Check cabinet power and earth connections. Try to reset the RIO Module. If this
does not help, replace the module.
RIO: On-board reference voltage error (restart required)
Description:
Testing of a internally generated vital CPU voltage has failed.
Possible
consequences:
This may influence the channel I/O-values.
Corrective
actions:
Check cabinet power and earth connections. Try to restart the RIO Module.
If this does not help, replace the module.
RIO: On-board voltage error. GND1 (reset required)
Description:
An internal PCB ground level identified as GND1 is out of limits.
Possible
consequences:
All affected IO channels are marked with error, and if input, values are frozen to
last valid value until the problem is solved and a manual reset is activated.
Corrective
actions:
Check cabinet power and earth connections. Try to reset the RIO Module. If this
does not help, replace the module.
RIO: On-board voltage error. GND2 (reset required)
Description:
An internal PCB ground level identified as GND2 is out of limits.