Message explanations
A-30
385585/C
Internal voltage test circuit error (see message)
Description:
The self-test circuit for internal PS (Process Station) voltages is reporting error.
Possible
consequences:
This alarm means that the PS (Process Station) is no longer capable of detecting
value out of limits for one or more of its internal reference voltages. This will in
itself not cause any problems for functionality, but may be an indication that HW
components are unreliable and that other failures may follow.
Corrective
actions:
•
Check power supplies connected to the PS (Process Station) rack/cabinet.
•
Some extra information is found in a system message received
simultaneously as the alarm ("Internal test circuit error xxx"). Try to replace
the PS. Note the alarm text, describe the current operation executed and
enclose this data when delivering the PS to Kongsberg Maritime Service.
•
Contact Kongsberg Maritime Service if this does not solve the problem.
Invalid external connections
Description:
This message shall not occur during normal operation, but is intended to be an aid
for the software engineer during configuration/commissioning.
Possible
consequences:
The system might not function properly.
Corrective
actions:
•
Check configuration.
•
Should this message occur during normal operation, contact Kongsberg
Maritime Service.
Invalid internal connections
Description:
This message shall not occur during normal operation, but is intended to be an aid
for the software engineer during configuration/commissioning.
Possible
consequences:
The system might not function properly.
Corrective
actions:
•
Check configuration.
•
Should this message occur during normal operation, contact Kongsberg
Maritime Service.
IO block linking failed
Description:
This message shall not occur during normal operation, but is intended to be an aid
for the software engineer during configuration/commissioning.
Corrective
actions:
Should the message occur during normal operation, contact Kongsberg Maritime
service.