Goodrive350-19 series VFD for crane
Communication protocol
-424-
Parameter
address
VFD
address
Write
command
CRC
Parameter
data
03
06
00 03
27 10
62 14
If the operation is successful, the following response is returned (same as the command transmitted
by the master):
Parameter
address
VFD
address
Write
command
CRC
Parameter
data
03
06
00 03
27 10
62 14
Note: In the preceding command description, spaces are added to a command just for
explanatory purposes. In practical applications, no space is required in the commands.
10.4.8.3 Example of continuously writing command 10H
Example 1: Set the VFD whose address is 01H to be forward running at the frequency of 10 Hz. Refer
to the table of other function parameters, the address of "Communication-based control command" is
2000H, 0001H indicates forward running, and the address of "Communication-based value setting" is
2001H, as shown in the following figure. 10 Hz is 03E8H in the hexadecimal form.
Function
Address
Data description
R/W
Communication-based
control command
2000H
0001H: Run forward
R/W
0002H: Run reversely
0003H: Jog forward
0004H: Jog reversely
0005H: Stop
0006H: Coast to stop (in emergency)
0007H: Fault reset
0008H: Jogging to stop
Communication-based
setting address
2001H
Communication-based frequency setting (0
–Fmax;
unit: 0.01 Hz)
R/W
2002H
PID reference (0
–1000, in which 1000 corresponds
to 100.0%)
In the actual operation, set P00.01 to 2 and P00.06 to 8.
The command transmitted by the master is as follows:
Parameter
address
VFD
address
Continuous
write
command
Number of
bytes
Parameter
quantity
01
10
20 00
00 02
04
Froward
running
00 01
10 Hz
03 E8
CRC
3B 10
If the operation is successful, the following response is returned:
Parameter
address
VFD
address
Continuous
write
command
CRC
Parameter
quantity
01
10
20 00
00 02
4A 08