Goodrive350-19 series VFD for crane
Function parameter list
-247-
Function
code
Name
Description
Default
Modify
delay
Y electric level
Y valid
Invalid
Switch on
delay
invalid
Valid
Switch off
delay
Setting range: 0.000
–50.000s
Note:
are valid only when
=1.
P06.10
RO1 switch-on
delay
0.000s
○
P06.11
RO1 switch-off
delay
0.000s
○
P06.12
RO2 switch-on
delay
0.000s
○
P06.13
RO2 switch-off
delay
0.000s
○
P06.14
AO1 output
0: Running frequency (0
–Max. output frequency)
1: Set frequency (0
–Max. output frequency)
2: Ramp reference frequency (0
–Max. output
frequency)
3: Rotational speed (0
–Speed corresponding to
max. output frequency)
4: Output (0
–Twice the inverter unit rated
current)
5: Output current (0
–Twice the motor rated
current)
6: Output (0
–1.5 times the inverter unit rated
voltage)
7: Output power (0
–Twice the motor rated
power)
8: Set torque (0
–Twice the motor rated torque)
9: Output torque (Actual 0
–Twice the motor
rated torque)
10: AI1 input (0
–10V/0–20mA)
11: AI2 input (0
–10V)
12: AI3 input (0
–10V/0–20mA)
13: HDIA input (0.00
–50.00kHz)
14: Value 1 set through Modbus communication
(0
–1000)
15: Value 2 set through Modbus communication
(0
–1000)
16: Value 1 set through
PROFIBUS/CANopen/DeviceNet
communication (0
–1000)
17: Value 2 set through
0
○
P06.16
HDO high-speed
pulse output
0
○