Goodrive350-19 series VFD for crane
Optional peripheral accessories
-492-
VFD model
Recommended
cable size (mm
2
)
Connectable cable size (mm
2
)
Terminal
screw
Fastening
torque
(Nm)
RST
UVW
PE
RST
UVW
P1
(+)
PB
(+) (-)
PE
–150*4P –150*4P –150*4P –150*2P
GD350-19-355G-4
95*4P
95*4P
95*4P
–150*4P
95*4P
–150*4P
95*4P
–150*4P
95*2P
–150*2P
GD350-19-400G-4
150*4P 150*2P
95*4P
–150*4P
95*4P
–150*4P
95*4P
–150*4P
95*2P
–150*2P
GD350-19-450G-4
150*4P 150*2P
95*4P
–150*4P
95*4P
–150*4P
95*4P
–150*4P
95*2P
–150*2P
GD350-19-500G-4
150*4P 150*2P
95*4P
–150*4P
95*4P
–150*4P
95*4P
–150*4P
95*2P
–150*2P
Note:
Cables of the sizes recommended for the main circuit can be used in scenarios where the
ambient temperature is lower than 40°C, the wiring distance is shorter than 100m, and the
current is the rated current.
The terminals P1, (+), PB, and (-) are used to connect to DC reactors and braking accessories.
Table D-2 AC 3PH 520V(-15%)
–690V(+10%)
VFD model
Recommended
cable size (mm
2
)
Connectable cable size (mm
2
)
Terminal
screw
Fastening
torque
(Nm)
RST
UVW
PE
RST
UVW
P1
(+)
PB
(+) (-)
PE
GD350-19-022G-6
10
10
10
–16
6
–16
6
–10
10
–16
M8
9
–11
GD350-19-030G-6
10
10
10
–16
6
–16
6
–10
10
–16
M8
9
–11
GD350-19-037G-6
16
16
16
–25
16
–25
6
–10
16
–25
M8
9
–11
GD350-19-045G-6
16
16
16
–25
16
–35
16
–25
16
–25
M8
9
–11
GD350-19-055G-6
25
16
16
–25
16
–35
16
–25
16
–25
M10
18
–23
GD350-19-075G-6
35
16
35
–50
25
–50
25
–50
16
–50
M10
18
–23
GD350-19-090G-6
35
16
35
–50
25
–50
25
–50
16
–50
M10
18
–23
GD350-19-110G-6
50
25
50
–95
50
–95
25
–95
25
–95
M10
18
–23
GD350-19-132G-6
70
35
70
–95
70
–95
25
–95
35
–95
M10
18
–23
GD350-19-160G-6
95
50
95
–150
95
–150
25
–150
50
–150
Nuts are used for
terminals. You are
recommended to use a
GD350-19-185G-6
95
50
95
–150
95
–150
25
–150
50
–150
GD350-19-200G-6
120
70
120
–300 120–300 35–300
70
–240