Goodrive350-19 series VFD for crane
Function parameter list
-275-
Function
code
Name
Description
Default
Modify
Y,
RO1, RO2
Output current
Overload pre-alarm
threshold
Time t
Time t
Pre-alarm time t
Pre-alarm time t
setting range:
Enable and define overload pre-alarm function
of the VFD and motor.
Setting range: 0x0000
–0x1132
Ones place:
0: Motor OL/UL pre-alarm, relative to motor
rated current.
1: VFD OL/UL pre-alarm, relative to VFD rated
output current.
2: Motor output torque overload/underload
pre-alarm, relative to motor rated torque.
Tens place:
0: The VFD continues to work for an OL/UL
alarm.
1: The VFD continues to work for a UL alarm but
stops running for an OL fault.
2: The VFD continues to work for an OL alarm
but stops running for a UL fault.
3. The VFD stops running for an OL/UL alarm.
Hundreds place:
0: Detect all the time.
1: Detect during constant speed running.
Thousands place: VFD overload current
reference selection
0: Related to current calibration coefficient
1: Irrelated to current calibration coefficient
–200% (relative