Goodrive350-19 series VFD for crane
Basic operation guidelines
-175-
Setting
Function
Description
28
C_AO1 from the PLC
1000 corresponds to 100.0%.
29
C_AO2 from the PLC
1000 corresponds to 100.0%.
30
Rotational speed
0
–Twice the motor rated synchronous
rotation speed
31
Output torque
0
–Twice the motor rated torque
32
Temperature measured by resistor
33
–47
Reserved
Related parameter list:
Function
code
Name
Description
Default
P06.00
HDO output type
0: Open collector high-speed pulse output
1: Open collector output
0
P06.14
AO1 output
0
–47
0
P06.15
Reserved
0
P06.16
HDO high-speed pulse output
0
P06.17
AO1 output lower limit
-300.0%
–P06.19
0.0%
P06.18
AO1 output corresponding to
lower limit
0.00V
–10.00V
0.00V
P06.19
AO1 output upper limit
P06.17
–100.0%
100.0%
P06.20
AO1 output corresponding to
upper limit
0.00V
–10.00V
10.00V
P06.21
AO1 output filter time
0.000s
–10.000s
0.000s
P06.27
HDO output lower limit
-300.0%
–P06.29
0.0%
P06.28
HDO output corresponding to
lower limit
0.00
–50.00Hz
0.0kHz
P06.29
HDO output upper limit
P06.27
–100.0%
100.0%
P06.30
HDO output corresponding to
upper limit
0.00
–50.00kHz
50.00kHz
P06.31
HDO output filter time
0.000s
–10.000s
0.000s
6.5.11 Digital input
The VFD carries four programmable digital input terminals and two HDI input terminals. The function
of all the digital input terminals can be programmed through function codes. HDI input terminal can be
set to act as high-speed pulse input terminal or common digital input terminal; if it is set to act as
high-speed pulse input terminal, you can also set HDIA or HDIB high-speed pulse input to serve as
the frequency reference and encoder signal input.