Function parameter list
-240-
Function
code
Name
Description
Default
Modify
COM
K
SB2
SB1
FWD
REV
SIn
The direction control is as follows during
running:
Sin
REV
Previous
direction
Present
direction
ON
OFF→ON
FWD run
REV run
REV run
FWD run
ON
ON→OFF
REV run
FWD run
FWD run
REV run
ON→
OFF
ON
Decelerate to stop
OFF
Sin: Three-wire control; FWD: Forward running;
REV: Reverse running
3: Three-wire control 2. This mode defines Sin
as the enabling terminal, and the running
command is generated by FWD or REV, but the
direction is controlled by both FWD and REV.
During running, the Sin terminal needs to be
closed, and terminal FWD or REV generates a
rising edge signal to control the running and
direction of the VFD; the VFD needs to be
stopped by disconnecting terminal Sin.