Goodrive350-19 series VFD for crane
Basic operation guidelines
-171-
Function
code
Name
Description
Default
DOWN terminal
P17.00
Set frequency
0.00Hz
–P00.03 (Max. output frequency)
0.00Hz
P17.02
Ramp reference frequency 0.00Hz
–P00.03 (Max. output frequency)
0.00Hz
P17.14
Digital adjustment value
0.00Hz
–P00.03 (Max. output frequency)
0.00Hz
6.5.9 Analog input
The VFD carries two analog input terminals AI1 and AI2, in which AI1 is0
–10V/0–20mA and whether
AI1 uses voltage input or current input can be set by P05.50, and AI2 is -10
–10V, and two high-speed
pulse input terminals. Each input can be filtered separately, and the corresponding reference curve
can be set by adjusting the reference corresponds to the max. value and min. value.
AI1
HDIB
P05.24
P05.25
P05.26
P05.27
P05.39
P05.40
P05.41
P05.42
P05.45
P05.46
P05.47
P05.48
P05.43
P05.28
P05.49
P17.19
P17.22
AI2
P05.29
P05.30
P05.31
P05.32
P05.33
P05.34
P05.35
P05.36
P05.37
P17.20
P05.00
(
HDIB input type
)
0
1
1
2
0
P05.44
(HDIB high-speed pulse input function
selection)
AI1 input voltage
AI2 input voltage
HDIB input frequency
AI1/AI2/HDI
P05.00
Ones
:
0: HDIA is high-speed pulse input
1: HDIA is digital input
P05.38
0: Set input via frequency
1: Reserved
2: Input via encoder
Analog input curve setting
Analog input filter
P05.00
Tens
:
0: HDIB is high-speed pulse input
1: HDIB is digital input
P05.44
0: Set input via frequency
1: Reserved
2: Input via encoder
HDIA
P17.21
0
1
1
2
0
P05.38
(HDIA high-speed pulse input function
selection)
HDIA input frequency
P05.00
(
HDIA input type
)
Related parameter list:
Function
code
Name
Description
Default
P05.00
HDI input type
0x00
–0x11
Ones place: HDIA input type
0: HDIA is high-speed pulse input
0x00