Goodrive350-19 series VFD for crane
Commissioning guidelines
-46-
closed-loop vector control. To switch the application macro and motor control mode, do as follows:
1. Set P90.00=2 (Lifting in closed-loop vector control), and set P90.01=1 (Lifting in open-loop vector
control).
2. Set P90.03=5 (Switch to SVC1 control).
3. Set S terminal function 62 to SVC1.
4. When the S terminal is invalid, the motor uses P90.00=2; when the S terminal is valid, the motor
uses P90.01=1.
5.3 Horizontal moving
5.3.1 Wiring
(+)
PB
VFD
R
S
T
R
S
T
M
3~
U
V
W
PE
VFD fault output
Brake output
RO1A
RO1B
RO1C
RO2A
RO2B
RO2C
Y1
CME
HDO
COM
CME
+24V
Braking resistor
PW
+24V
S1
S2
S4
FWD run
REV run
Multi-step run terminal 1
Multi-step run terminal 2
COM
Fault reset
Coast to stop
S5
S6
COM
EC-IO-502-00
IO expansion card
PW
+24V
S7
S8
Multi-step run terminal 3
Figure 5-3 Wiring for horizontal moving
Note: If the wiring is performed according to Figure 5-3, most VFD parameters need no adjustment. If
the onsite function terminals are inconsistent with the terminals shown in the figure, adjust the input
and output terminal functions according to the actual wiring after selecting this application macro.