Goodrive350-19 series VFD for crane
Function parameter list
-274-
Function
code
Name
Description
Default
Modify
0: OL2 is valid.
1: OL2 is invalid.
2: Reserved
Note: It can be modified only when
is 1
indicating special functions are enabled.
P11.06
Automatic current
limit threshold
Current-limit protection function detects output
current during running, and compares it with the
current-limit level defined by
, if it
exceeds the current-limit level, the VFD will run
at stable frequency during accelerated running,
or run in decreased frequency during
constant-speed running; if it exceeds the
current-limit level continuously, the VFD output
frequency will drop continuously until reaching
lower limit frequency. When the output current is
detected to be lower than the current-limit level
again, it will continue accelerated running.
Output current A
Output frequency f
Current-limit
threshold
Set
frequency
Acceleration
Constant
speed
Time t
Time t
setting range: 50.0
–250.0% (of the rated
VFD output current)
setting range: 0.00
–50.00Hz/s
250.0%
◎
P11.07
Frequency drop
rate during current
limit
10.00
Hz/s
◎
P11.08
VFD/motor OL/UL
pre-alarm
selection
If the VFD or motor output current is larger than
the overload pre-alarm detection level (
),
and the duration exceeds the overload
pre-alarm detection time (
), overload
pre-alarm signal will be outputted.
0x0000
○
P11.09
Overload
pre-alarm
detection level
150%
○
P11.10
Overload
pre-alarm
detection time
1.00s
○