Goodrive350-19 series VFD for crane
Function parameter list
-263-
Function
code
Name
Description
Default
Modify
2: Valid during running, cleared after a stop
command is received
P08.45
Frequency
increment integral
rate of the UP
terminal
0.01
–50.00Hz/s
0.50Hz/s
○
P08.46
Frequency
integral rate of the
DOWN terminal
0.01
–50.00Hz/s
0.50Hz/s
○
P08.47
Action selection at
power-off during
frequency setting
0x000
–0x111
Ones place: Action selection at power-off during
frequency adjusting through digitals.
0: Save the setting at power-off.
1: Clear the setting at power-off.
Action selection at power-off during frequency
adjusting through Modbus communication
0: Save the setting at power-off.
1: Clear the setting at power-off.
Hundreds place: Action selection at power-off
during frequency adjusting through DP
communication methods
0: Save the setting at power-off.
1: Clear the setting at power-off.
0x000
○
P08.48
Initial electricity
consumption
high-order bits
Used to set the initial electricity consumption.
Initial electricity consumption =
*1000 +
setting range: 0
–59999 kWh (k)
setting range: 0.0
–999.9 kWh
0 kWh
○
P08.49
Initial electricity
consumption
low-order bits
0.0 kWh
○
P08.50
Magnetic flux
braking
Used to enable magnetic flux braking.
0: Disable
100
–150: A larger coefficient indicates stronger
braking.
The VFD can quickly slow down the motor by
increasing the magnetic flux. The energy
generated by the motor during braking can be
transformed into heat energy by increasing the
magnetic flux.
0
○