Goodrive300-01 inverter for air compressor Function parameters
-18-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
above, too low carrier frequency will cause unstable
running, torque decreasing and surge.
The manufacturer has set a reasonable carrier
frequency when the inverter is in factory. In general,
users do not need to change the parameter.
When the frequency in use exceeds the default
carrier frequency, the inverter needs to derate 10%
for each additional 1k carrier frequency.
The setting range: 1.0~15.0kHz
P00.15
Motor parameter
autotuning
0: No operation
1: Rotation autotuning
Comprehensive motor parameter autotuning
It is recommended to use rotation autotuning when
high control accuracy is needed.
2: Static autotuning 1 (autotune totally)
It is suitable in the cases when the motor cannot
decouple from the load.
3: Static autotuning 2 (autotune
partially)
When the current motor is motor 1, autotune P02.06,
P02.07, P02.08; when the current motor is motor 2,
autotune P12.06, P12.07, P12.08.
0
◎
P00.16
AVR function
selection
0: Invalid
1: Valid during the whole procedure
The auto-adjusting function of the inverter can
cancel the impact on the output voltage of the
inverter because of the bus voltage fluctuation.
1
○
P00.17
Reserved
Reserved
0
◎
P00.18
Function
parameters
restore
0: No operation
1: Restore to the default value
2: Cancel the fault record
Note: The function code will restore to 0 after
finishing the operation of the selected function
code. Restoring to the default value will cancel
the user password, please use this function with
caution.
0
◎
P01 Group Start-up and stop control
P01.00
Start mode
0: Start-up directly: start from the starting frequency
P01.01
1: Start-up after DC braking: start the motor from the
0
◎