Goodrive300-01 inverter for air compressor Function parameters
-73-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
0: No check (N, 8, 1) for RTU
1: Even check (E, 8, 1) for RTU
2: Odd check (O, 8, 1) for RTU
3: No check (N, 8, 2) for RTU
4: Even check (E, 8, 2) for RTU
5: Odd check(O, 8, 2) for RTU
P14.03
Answer delay
0~200ms
The interval time when the inverter receives the data
and sends it to the upper computer. If the answer
delay is shorter than the system processing time,
then the answer delay time is the system processing
time; if the answer delay is longer than the system
processing time, then after the system deals with the
data, the inverter will not send the data to the upper
computer until reaching the answer delay time.
5
○
P14.04
Fault time of
communication
overtime
0.0 (invalid), 0.1~60.0s
When the function code is set as 0.0, the
communication overtime parameter is invalid.
When the function code is set as non-zero, if the
interval time between two communications exceeds
the communication overtime, the system will report
“485 communication fault” (CE).
Generally, set it as invalid; set the parameter in the
continuous communication to monitor the
communication state.
0.0s
○
P14.05
Transmission fault
processing
0: Alarm and coast to stop
1: No alarm and continue to run
2: No alarm and stop according to the stop mode
(only under the communication control)
3: No alarm and stop according to the stop mode
(under all control modes)
0
○
P14.06
Communication
processing
0x00~0x11
LED ones:
0: Write with response: the inverter will respond to all
read and write commands of the upper computer.
1: Write without response: the inverter only responds
to the read command other than the write command.
The communication efficiency can be increased by
this method.
0x00
○