Goodrive300-01 inverter for air compressor Function parameters
-13-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
Note: AM-Asynchronous motor
SM-Synchronous motor
P00.01
Run command
channel
Select the run command channel of the inverter.
The control command of the inverter includes:
start-up, stop, forward, reverse, jogging and fault
reset.
0: Keypad run command channel
(“LOCAL/REMOT”
light off)
Carry out the command control by RUN, STOP/RST
on the keypad. Set the multi-function key
QUICK/JOG to
FWD/REVC
shifting
function
(P07.02=3) to change the running direction;
press
RUN and STOP/RST simultaneously in running
state to make the inverter coast to stop
.
1: Terminal run command channel
(“LOCAL/REMOT” flickering)
Carry out the run command control by the forward
rotation, reverse rotation and forward jogging and
reverse jogging of the multi-function input terminals.
2: Communication run command channel
(“LOCAL/REMOT” on);
The run command is controlled by the upper
computer via communication.
0
○
P00.02
Communication
run commands
Select the controlling communication command
channel of the inverter.
0: MODBUS communication
1~3: Reserved
0
○
P00.03
Max. output
frequency
This parameter is used to set the maximum output
frequency of the inverter. Users should pay attention
to this parameter because it is the foundation of the
frequency setting and the speed of acceleration and
deceleration.
The setting range: P00.04~400.00Hz
50.00Hz
◎
P00.04
Upper limit of
running frequency
The upper limit of running frequency is the upper
limit of output frequency of the inverter which is
lower than or equal to the maximum output
frequency.
If the set frequency is above the upper limit, the
inverter runs at the upper limit.
50.00Hz
◎