Goodrive300-01 inverter for air compressor Function parameters
-80-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
maintenance of
component 4
Pre-alarm when the accumulated service time of
component 4 exceeds the set value; pre-alarm is
invalid when the set value=0.
P19.04
Set time for
maintenance of
component 5
0~65535h
Pre-alarm when the accumulated service time of
component 5 exceeds the set value; pre-alarm is
invalid when the set value=0.
0
●
P19.05
Time for use of
component 1
0~65535h
0
●
P19.06
Time for use of
component 2
0~65535h
0
●
P19.07
Time for use of
component 3
0~65535h
0
●
P19.08
Time for use of
component 4
0~65535h
0
●
P19.09
Time for use of
component 5
0~65535h
0
●
P19.10
Motor actual
output power
0.0~6553.6kW
0.0kW
●
P19.11 Current pressure 0.00~655.36Mpa
0.00Mpa
●
P19.12
Current
temperature
-20~150°C
0°C
●
P19.13
Signal state 1
BIT0: air filter blockage signal, 1: fault, 0: normal
BIT1: oil filter blockage signal, 1: fault, 0: normal
BIT2: separator blockage signal, 1: fault, 0: normal
BIT3: precision separator blockage signal, 1: fault, 0:
normal
BIT4: external fault signal 1, 1: fault, 0: normal
BIT5: external fault signal 2, 1: fault, 0: normal
BIT6: magnetic valve signal state, 1: load, 0: unload
BIT7: auxiliary motor state, 1: run, 0: stop
BIT8: pressure pre-alarm signal, 1: pressure
pre-alarm, 0: normal
BIT9: temperature pre-alarm signal, 1: temperature
pre-alarm, 0: normal
BIT10: pressure alarm signal, 1: pressure alarm, 0:
normal
BIT11: temperature alarm signal, 1: temperature
0
●