Goodrive300-01 inverter for air compressor Function parameters
-20-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
the inverter.
The setting range of P01.03: 0.0~100.0%
The setting range of P01.04: 0.00~50.00s
P01.05
ACC/DEC
selection
The changing mode of the frequency during start-up
and running.
0: Linear type
The output frequency increases or decreases
linearly.
1: Reserved
0
◎
P01.06
Reserved
Reserved
◎
P01.07
Reserved
Reserved
◎
P01.08
Stop mode
0: Decelerate to stop: after the stop command
becomes valid, the inverter decelerates to decrease
the output frequency during the set time. When the
frequency decreases to P01.15, the inverter stops.
1: Coast to stop: after the stop command becomes
valid, the inverter ceases the output immediately.
And the load coasts to stop at the mechanical inertia.
0
○
P01.09
Starting frequency
of DC braking
The starting frequency of stop braking: the inverter
will carry on stop DC braking when the frequency is
arrived during the procedure of decelerating to stop.
The waiting time of stop braking: before the stop DC
braking, the inverter will close output and begin to
carry on the DC braking after the waiting time. This
function is used to avoid the overcurrent fault caused
by DC braking when the speed is too high.
Stop DC braking current: the DC brake added. The
stronger the current, the bigger the DC braking
effect.
The braking time of stop braking: the retention time
of DC brake. If the time is 0, the DC brake is invalid.
The inverter will stop at the set deceleration time.
0.00Hz
○
P01.10
Waiting time of
DC braking
0.00s
○
P01.11
DC braking
current
0.0%
○
P01.12 DC braking time
0.00s
○