Goodrive300-01 inverter for air compressor Function parameters
-28-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
protection coefficient.
So, the bigger the value of K is, the smaller the value
of M is. When M=116%, the fault will be reported
after 1 hour; when M=200%, the fault will be reported
after 1 minute; when M>=400%, the fault will be
reported instantly.
The setting range: 20.0%~120.0%
P02.28
Correction
coefficient of
motor 1 power
Correct the power displaying of motor 1.
Only impact the displaying value other than the
control performance of the inverter.
The setting range: 0.00~3.00
1.00
○
P02.29
Parameter display
of motor 1
0: Display according to the motor type; in the mode,
only display the related parameters of current motor
type for the convenience of operation
1: Display all; in the mode, display all motor
parameters
0
○
P03 Group Vector control
P03.00
Speed loop
proportional gain1
The parameters P03.00~P03.05 only apply to vector
control mode. Below the switching frequency
1(P03.02), the speed loop PI parameters are:
P03.00 and P03.01. Above the switching frequency
2(P03.05), the speed loop PI parameters are:
P03.03 and P03.04. PI parameters are gained
according to the linear change of two groups of
parameters. It is shown as below:
20.0
○
P03.01
Speed loop
integral time1
0.200s
○
P03.02
Low switching
frequency
5.00Hz
○
P03.03
Speed loop
proportional gain
2
20.0
○
P03.04
Speed loop
integral time 2
0.200s
○
P03.05
High switching
frequency
10.00Hz
○