Goodrive300-01 inverter for air compressor Function parameters
-78-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
stable running.
P18.11
Lower limit of
loading running
frequency
P18.12~P00.04 (upper limit of running frequency)
During adjusting, allow to output the minimum
running frequency when the pressure is above the
set pressure and below the unloading pressure.
40.00Hz
○
P18.12
Non-load running
frequency
P01.15~P18.11 (Lower limit frequency of loaded
running)
The allowable output running frequency for air
compressor at no load.
38.00Hz
○
P18.13
Non-load delay
time
0~3600s
Enter into hibernation when non-load running
exceeds the set time.
60s
○
P18.14
Stop delay time
0~3600s
At stop, run by non-load frequency and then stop
after the delay time.
0s
○
P18.15 Loading delay time
0~3600s
The master runs for the time before loading
operation.
10s
○
P18.16 Restart delay time
0~3600s
After stop, the set time is needed for restart.
30s
○
P18.17
Pre-alarm
pressure
0.00~ P18.04
Pre-alarm when the air supply pressure is detected
above the set pressure.
0.90Mpa
○
P18.18
Alarm pressure
0.00~ P18.04
Alarm and stop when the air supply pressure is
detected above the set pressure.
1.00Mpa
○
P18.19
Pre-alarm
temperature
-20~150°C
Pre-alarm when the exhaust temperature is detected
above the set temperature.
105°C
○
P18.20 Alarm temperature
-20~150°C
Alarm and stop when the exhaust temperature is
detected above the set temperature.
110°C
○
P18.21
Low temperature
protection
threshold
-20~150°C
When the exhaust temperature is detected below the
set value, display the temperature is too low, prohibit
starting the air compressor and alarm.
-10°C
○
P18.22
Power correction
coefficient
0%~200%
100%
○