Goodrive300-01 inverter for air compressor Function parameters
-37-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
P04.29
Voltage
increasing time
Voltage increasing time is the time when the inverter
accelerates from the output minimum voltage to the
output maximum voltage.
Voltage decreasing time is the time when the inverter
decelerates from the output maximum voltage to the
output minimum voltage.
The setting range: 0.0~3600.0s
5.0s
○
P04.30
Voltage
decreasing time
5.0s
○
P04.31
Maximum output
voltage
Set the upper and low limit of the output voltage.
The setting range of P04.31: P04.32~100.0% (motor
rated voltage)
The setting range of P04.32: 0.0%~P04.31
100.0%
◎
P04.32
Minimum output
voltage
0.0%
◎
P04.33
Flux weakening
coefficient at
constant power
The parameter is used to adjust the output voltage of
inverter in SVPWM control mode at flux weakening.
Note: Invalid in constant torque mode.
The setting range of P04.33: 1.00~1.30
1.00
○
P04.34
Reactive
close-loop
proportionality
coefficient
0~3000
60
○
P04.35
Reactive
close-loop integral
coefficient
0~3000
20
○
P05 Group Input terminals
P05.00
Reserved
0
◎
P05.01
S1 terminals
function selection
0: No function
1: Forward rotation operation (FWD)
0
◎