Goodrive300-01 inverter for air compressor Function parameters
-44-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
8: Frequency arrival
9: Zero speed running
10: Upper limit frequency arrival
11: Lower limit frequency arrival
12: Ready for operation
13: Pre-magnetizing
14: Overload pre-alarm
15: Underload pre-alarm
16: Completion of simple PLC stage
17: Completion of simple PLC cycle
18: Setting count value arrival
19: Defined count value arrival
20: External fault valid
21: Length arrival
22: Running time arrival
23: MODBUS communication virtual terminals output
24: Reserved
25: Reserved
26: Reserved
27: Start-up and stop control of auxiliary motor
(specific for air compressor)
28: Output control of magnetic valve (specific for air
compressor)
29: Main motor cooling fan control (specific for air
compressor)
30: System fault (specific for air compressor)
P06.05
Polarity of output
terminals
The function code is used to set the polarity of the
output terminal.
When the current bit is set to 0, input terminal is
positive.
When the current bit is set to 1, input terminal is
negative.
BIT3
BIT2
BIT1
BIT0
RO2
RO1
RO4
RO3
The setting range: 00~0F
00
○
P06.06
RO3 switch-on
delay time
The function code defines the corresponding delay
time of the electrical level change during the
programmable terminal switching on and off.
0.000s
P06.07
RO3 switch-off
delay time
0.000s
○