Goodrive300-01 inverter for air compressor Function parameters
-40-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
1:2-wire control 2; Separate the enable from the
direction. FWD defined by this mode is the enabling
ones. The direction depends on the state of the
defined REV.
2:3-wire control 1; Sin is the enabling terminal on this
mode, and the running command is caused by FWD
and the direction is controlled by REV. Sin is
natural closed.
COM
K
SB2
SB1
FWD
REV
SIn
The direction control is as below during operation:
Sln
REV
Previous
direction
Current
direction
ON
OFF→ON
Forward
Reverse
Reverse
Forward
ON
ON→OFF
Reverse
Forward
Forward
Reverse
ON→OF
F
ON
Decelerate to stop
OFF
3:3-wire control 2; Sin is the enabling terminal on this
mode, and the running command is caused by SB1
or SB3 and both of them control the running
direction.NC SB2 generates the stop command.