Goodrive300-01 inverter for air compressor                                                                Function parameters

 

-38-

 

Function 

code 

Name 

Detailed instruction of parameters 

Default 

value 

Modif

P05.02 

S2 terminals 

function selection 

2: Reverse rotation operation (REV) 

3: 3-wire control operation (Sln) 

4: Forward jogging 

5: Reverse jogging 

6: Coast to stop   

7: Fault reset   

8: Operation pause   

9: External fault input   

10: Increasing frequency setting (UP) 

11: Decreasing frequency setting (DOWN) 

12: Frequency setting clear 

13: Shift between A setting and B setting 

14: Shift between combination setting and A setting   

15: Shift between combination setting and B setting   

16: Multi-step speed terminal 1   

17: Multi-step speed terminal 2 

18: Multi-step speed terminal 3 

19: Multi- step speed terminal 4 

20: Multi- step speed pause 

21: ACC/DEC time 1 

22: ACC/DEC time 2 

23: Simple PLC stop reset   

24: Simple PLC pause   

25: PID control pause 

26: Traverse pause (stop at the current frequency) 

27: Traverse reset (return to the center frequency) 

28: Counter reset   

29: Torque control disabling   

30: ACC/DEC disabling   

31: Counter triggering 

32: Length reset   

33: Cancel the frequency change setting temporarily 

34: DC brake   

35: Shift the motor 1 into motor 2 

36: Shift the command to the keypad   

37: Shift the command to the terminals   

38: Shift the command to the communication   

39: Pre-magnetized command   

40: Power consumption clear     

41: Power consumption hold   

42: Air filter blockage signal 

 

P05.03 

S3 terminals 

function selection 

 

P05.04 

S4 terminals 

function selection 

 

P05.05 

S5 terminals 

function selection 

 

P05.06 

S6 terminals 

function selection 

 

P05.07 

S7 terminals 

function selection 

 

P05.08 

S8 terminals 

function selection 

 

P05.09 

Reserved 

 

Содержание GD300-01-011G-4

Страница 1: ...Goodrive 300 01 Series Inverter for Air Compressor GD300 01 037G 4...

Страница 2: ...sses external logic signals completing all control and protect functions instead of traditional PLC functions The fan inverters realize speed regulation to maintain the machine in constant temperature...

Страница 3: ...meters 76 Chapter 4 Commissioning guidelines 82 4 1 Commissioning procedures for integrated system 82 4 1 1 Master inverter commissioning 82 4 1 2 Fan commissioning 82 4 1 3 System commissioning 82 Ap...

Страница 4: ...operation Qualified electricians People working on the device should have received professional electrical and safety training and passed relevant examination and be familiar with all steps and requir...

Страница 5: ...erials Connect the optional braking parts braking resistors braking units or feedback units according to the wiring diagram Do not operate on the inverter if damage or components missing occurred to t...

Страница 6: ...ly of the inverter frequently For inverters that have been stored for a long time check and adjust the capacitance and perform pilot run before operating on the inverter Cover the front board before r...

Страница 7: ...e 20ms sensorless vector control Torque control accuracy 10 sensorless vector control Starting torque Asynchronous motor 0 25Hz 150 sensorless vector control Synchronous motor 2 5 Hz 150 sensorless ve...

Страница 8: ...input 20 150 C Digital input 8 common inputs the Max frequency 1kHz internal impedance 3 3k 1 high speed input the Max frequency 50kHz Relay output 2 programmable NO outputs 2 programmable NO NC outpu...

Страница 9: ...10 2 4 Rated specifications Model Rated output power kW Rated input current A Rated output current A GD300 01 7R5G 4 7 5 25 18 5 GD300 01 011G 4 11 32 25 GD300 01 015G 4 15 32 32 GD300 01 018G 4 18 5...

Страница 10: ...erence null potential AI1 1 Input range AI1 AI2 voltage and current can be chosen 0 10V 0 20mA AI1 can be shifted by J3 AI2 can be shifted by J4 AI3 10V 10V 2 Input impedance Voltage input 20k current...

Страница 11: ...irection input terminal supporting both NPN and PNP 4 Max input frequency 1kHz 5 All are programmable digital input terminals Users can set the terminal function through function codes S2 Switch input...

Страница 12: ...Goodrive300 01 inverter for air compressor Product overview 11 2 5 3 Wiring diagram...

Страница 13: ...fied at stopping and running state means the setting value of the parameter cannot be modified at running state means the value of the parameter is the real detection value which cannot be modified Th...

Страница 14: ...by the forward rotation reverse rotation and forward jogging and reverse jogging of the multi function input terminals 2 Communication run command channel LOCAL REMOT on The run command is controlled...

Страница 15: ...eypad to modify the frequency by the keypad 1 AI1 2 AI2 3 AI3 Set the frequency by analog input terminals Goodrive300 01 series inverters provide 3 analog input terminals as the standard configuration...

Страница 16: ...lti step speed running The inverter runs at multi step speed mode when P00 06 6 or P00 07 6 Set P05 to select the current running step and set P10 to select the current running frequency The multi ste...

Страница 17: ...set frequency Note The combination manner can be shifted by P5 terminal function 0 P00 10 Keypad setting frequency When A and B frequency commands are selected as Keypad setting the value of the funct...

Страница 18: ...sed with caution after commissioning if the change of rotation direction is disabled 2 Forbid to run in reverse direction It can be used in some special cases if the reverse running is disabled P00 14...

Страница 19: ...It is suitable in the cases when the motor cannot decouple from the load 3 Static autotuning 2 autotune partially When the current motor is motor 1 autotune P02 06 P02 07 P02 08 when the current moto...

Страница 20: ...ntion time of the starting frequency Set a proper starting frequency to increase the torque of the inverter during starting During the retention time of the starting frequency the output frequency of...

Страница 21: ...d the inverter ceases the output immediately And the load coasts to stop at the mechanical inertia 0 P01 09 Starting frequency of DC braking The starting frequency of stop braking the inverter will ca...

Страница 22: ...ting range 0 0 3600 0s 0 0s P01 14 Shifting between FWD REV rotation Set the threshold point of the inverter 0 Switch after zero frequency 1 Switch after the starting frequency 2 Switch after the spee...

Страница 23: ...tected to be valid during powering on the system will start the inverter automatically after the initialization Note This function should be selected with cautions or serious result may follow 0 P01 1...

Страница 24: ...eed is met the inverter will run automatically after waiting for the time defined by P01 22 0 P01 22 The waiting time of restart after power off The function determines the waiting time before the aut...

Страница 25: ...e name plate To guarantee the control performance configure the motor as the standard motor If the motor power has a great gap between the standard the control performance of the inverter will decreas...

Страница 26: ...nt 2 of AM1 iron core 0 0 100 0 68 0 P02 13 Magnetic saturation coefficient 3 of AM1iron core 0 0 100 0 57 0 P02 14 Magnetic saturation coefficient 4 of AM1 iron core 0 0 100 0 40 0 P02 15 Rated power...

Страница 27: ...ters for high performance vector control the parameters have a direct impact on the control performance When P00 15 1 rotation autotuning in no need of change P02 23 will update via autotuning when P0...

Страница 28: ...rotection 1 Common motor with low speed compensation Because the heat releasing effect of the common motors will be weakened the corresponding electric heat protection will be adjusted properly The lo...

Страница 29: ...splay of motor 1 0 Display according to the motor type in the mode only display the related parameters of current motor type for the convenience of operation 1 Display all in the mode display all moto...

Страница 30: ...of the system Adjust on the base of PI according to different loads to meet various demands The setting range of P03 00 0 200 0 The setting range of P03 01 0 000 10 000s The setting range of P03 02 0...

Страница 31: ...2kW 4000 2000 160 200 kW P03 10 Current loop integral coefficient 1 1000 P03 11 Torque setting This parameter is used to enable the torque control mode and set the torque 0 Torque control is invalid 1...

Страница 32: ...g for upper frequency of REV rotation in torque control 50 00 Hz P03 18 Upper electromotion torque source This function code is used to select the electromotion and braking torque upper limit source 0...

Страница 33: ...3 23 10 100 P03 24 Max voltage limit P03 24 sets the maximum voltage of the inverter which is dependent on the site situation The setting range 0 0 120 0 100 0 P03 25 Pre exciting time Carry out motor...

Страница 34: ...l set by P04 27 Note Vb in the below picture is the motor rated voltage and fb is the motor rated frequency P04 01 Torque boost of motor 1 To compensate the feature of low frequency torque carry out t...

Страница 35: ...current stall or protection of the inverter The setting range of P04 03 0 00Hz P04 05 The setting range of P04 04 0 0 110 0 the rated voltage of motor 1 The setting range of P04 05 P04 03 P04 07 The s...

Страница 36: ...These phenomena can be canceled by adjusting this parameter The setting range of P04 10 0 100 The setting range of P04 11 0 100 The setting range of P04 12 0 00Hz P00 03 Max output frequency 10 P04 11...

Страница 37: ...ng range of P04 25 0 00Hz P00 03 Max output frequency 10 P04 24 Vibration control factor at high frequency of motor 2 10 P04 25 Vibration control threshold of motor 2 30 00Hz P04 26 Energy saving oper...

Страница 38: ...1 Maximum output voltage Set the upper and low limit of the output voltage The setting range of P04 31 P04 32 100 0 motor rated voltage The setting range of P04 32 0 0 P04 31 100 0 P04 32 Minimum outp...

Страница 39: ...20 Multi step speed pause 21 ACC DEC time 1 22 ACC DEC time 2 23 Simple PLC stop reset 24 Simple PLC pause 25 PID control pause 26 Traverse pause stop at the current frequency 27 Traverse reset retur...

Страница 40: ...T2 BIT1 BIT0 S5 S4 S3 S2 S1 The setting range 0x000 0x1FF 0x000 P05 11 ON OFF filter time Set the sample filter time of S1 S8 and HDI terminals If the interference is strong increase the parameter to...

Страница 41: ...l on this mode and the running command is caused by FWD and the direction is controlled by REV Sin is natural closed COM K SB2 SB1 FWD REV SIn The direction control is as below during operation Sln RE...

Страница 42: ...nceled Only when FWD REV is relaunched the inverter can start again For example the valid STOP RST stop when PLC signal cycles stop fixed length stop and terminal control see P07 04 P05 14 Switch on d...

Страница 43: ...een the analog input voltage and its corresponding set value If the analog input voltage exceeds the set minimum or maximum input value the inverter will count at the minimum or maximum one When the a...

Страница 44: ...10 00V The setting range of P05 40 100 0 100 0 The setting range of P05 41 0 000s 10 000s The setting range of P05 42 10 00V P05 44 The setting range of P05 43 100 0 100 0 The setting range of P05 44...

Страница 45: ...eserved 25 Reserved 26 Reserved 27 Start up and stop control of auxiliary motor specific for air compressor 28 Output control of magnetic valve specific for air compressor 29 Main motor cooling fan co...

Страница 46: ...ing rotation speed 4 Output current relative to twice the inverter rated current 5 Output current relative to twice the motor rated current 6 Output voltage 7 Output power 8 Set torque value 9 Output...

Страница 47: ...06 24 The setting range of P06 23 0 00 10 00V The setting range of P06 24 P06 22 100 0 The setting range of P06 25 0 00 10 00V The setting range of P06 26 0 000 10 000s P06 27 P6 31 Reserved 0 00V P06...

Страница 48: ...load the local function parameter to the keypad 2 Download the keypad function parameter to local address including the motor parameters 3 Download the keypad function parameter to local address exclu...

Страница 49: ...run command channels 0 Keypad control terminals control communication control 1 Keypad control terminals control 2 Keypad control communication control 3 Terminals control communication control 0 P07...

Страница 50: ...g state 0x0000 0xFFFF BIT0 set frequency Hz on frequency flickering slowly BIT1 bus voltage V on BIT2 input terminals state BIT3 output terminals state BIT4 PID reference flickering BIT5 PID feedback...

Страница 51: ...0 0 999 9 kWh P07 16 Low bit of power consumption P07 17 Reserved Reserved P07 18 The rated power of the inverter 0 4 3000 0kW P07 19 The rated voltage of the inverter 50 1200V P07 20 The rated curren...

Страница 52: ...fline fault PIDE 23 Braking unit fault bCE 24 Running time arrival END 25 Electrical overload OL3 26 Panel communication fault PCE 27 Parameter uploading fault UPE 28 Parameter downloading fault DNE 2...

Страница 53: ...age at previous 2 fault 0 0V P07 54 Max temperature at previous 2 fault 0 0 C P07 55 Input terminals state at previous 2 fault 0 P07 56 Output terminals state at previous 2 fault 0 P08 Group Enhanced...

Страница 54: ...00Hz P08 14 Jumping frequency range 3 0 00Hz P08 15 Bus voltage pre protection function Bus voltage pre protection function 0 3 BIT0 1 Enable 0 Close voltage pre protection function 0 P08 16 Low volt...

Страница 55: ...eset times Fault reset times Set the automatic fault reset times If the reset time exceeds this set value the inverter will stop to wait maintenance Interval time of automatic fault reset The interval...

Страница 56: ...Below is the waveform diagram Setting range of P08 32 0 00Hz P00 03 Max output frequency Setting range of P08 33 100 0 100 0 FDT1 electrical level Setting range of P08 34 0 00Hz P00 03 Max output fre...

Страница 57: ...1180V 380V voltage 700 0V 500V voltage 900 0V 660V voltage 1120 0V P08 39 Cooling fan running mode 0 Normal mode 1 The fan keeps running after power on 0 P08 40 PWM selection 0x00 0x21 LED ones PWM m...

Страница 58: ...mmand LED thousands keys and digital potentiometer integral function 0 The integral function is valid 1 The integral function is invalid P08 43 Integral ratio of the keypad potentiometer 0 01 10 00s 0...

Страница 59: ...08 48 1000 P08 49 Setting range of P08 48 0 59999kWh k Setting range of P08 49 0 0 999 9 kWh 0 P08 49 Low bit of initial power consumption 0 0 P08 50 Magnetic flux braking This function code is used t...

Страница 60: ...ID control The parameter determines the target reference channel of procedure PID 0 Keypad P09 01 1 AI1 2 AI2 3 AI3 4 HDI 5 Multi step speed 6 MODBUS communication 7 Reserved 8 Reserved 9 Reserved 10...

Страница 61: ...nal gain P of PID input P determines the strength of the whole PID adjuster The parameter of 100 means that when the deviation of PID feedback and reference is 100 the adjusting range of PID adjustor...

Страница 62: ...e loop reference As shown in the diagram below PID adjustor stops to work during the deviation limit Set the function properly to adjust the accuracy and stability of the system Setting range 0 0 100...

Страница 63: ...adjustment when the frequency reaches the upper and low limit If the integration keeps stable and the trend between the reference and feedback changes the integration will change with the trend quickl...

Страница 64: ...sudden power loss Setting range 0 00Hz s P00 03 Max output frequency After the power loss of the grid the bus voltage drops to the sudden frequency decreasing point and the inverter begins to decrease...

Страница 65: ...ult and the inverter trips Ones current limit action selection 0 Invalid 1 Valid Tens overload alarm of hardware current limit 0 Valid 1 Invalid 01 P11 06 Automatic current limit During the running of...

Страница 66: ...Overload pre alarm of the inverter relative to the rated current of the inverter LED tens 0 The inverter continues to work after overload and underload pre alarm 1 The inverter continues to work after...

Страница 67: ...ed deviation detection 0 0 50 0 Set the speed deviation detection 10 0 P11 15 Speed deviation detection time Set the speed deviation detection time Setting range of P11 15 0 0 10 0s 0 0s P11 16 Automa...

Страница 68: ...05 on model P12 04 Rated voltage of AM2 0 1200V Depend on model P12 05 Rated current of AM2 0 8 6000 0A Depend on model P12 06 Stator resistor of AM2 0 001 65 535 After motor parameter autotuning the...

Страница 69: ...setting of motor parameters on the name plate To guarantee the control performance configure the motor as the standard motor If the motor power has a great gap between the standard the control perform...

Страница 70: ...When P00 15 2 the set value of P12 23 cannot be updated by autotuning please count according to the following method The counter electromotive force constant can be counted according to the parameters...

Страница 71: ...will be reported after 1 hour when M 200 the fault will be reported after 1 minute when M 400 the fault will be reported instantly The setting range 20 0 120 0 100 0 P12 28 Correction coefficient of...

Страница 72: ...alid frequency shifting point between source current 1 and current 2 Setting range 0 00Hz P00 03 Max output frequency 30 00 Hz P13 05 Superposition frequency reserved 200 1000Hz 500Hz P13 06 Pulse sup...

Страница 73: ...is writing the frame the communication address of the slave is set to 0 the address is the communication address All slaves on the MODBUS bus can receive the frame but the salve does not respond The...

Страница 74: ...time 0 0 invalid 0 1 60 0s When the function code is set as 0 0 the communication overtime parameter is invalid When the function code is set as non zero if the interval time between two communication...

Страница 75: ...he motor Range 0 65535RPM 0RPM P17 06 Torque current Display current torque current of the inverter Range 0 0 3000 0A 0 0A P17 07 Exciting current Display current exciting current of the inverter Rang...

Страница 76: ...Length Display the current length of the inverter Range 0 65535 0 P17 18 Counting value Display the current counting value of the inverter Range 0 65535 0 P17 19 AI1 input voltage Display analog AI1 i...

Страница 77: ...Exciting current reference Display the exciting current reference in the vector control mode Range 3000 0 3000 0A 0 0A P17 34 Torque current reference Display the torque current reference in the vect...

Страница 78: ...it of pressure sensor 0 00 20 00 1 60Mpa P18 05 Unloading pressure 0 00 P18 04 Under automatic mode after the air compressor starts unload automatically when the air supply pressure is higher than the...

Страница 79: ...hen stop after the delay time 0s P18 15 Loading delay time 0 3600s The master runs for the time before loading operation 10s P18 16 Restart delay time 0 3600s After stop the set time is needed for res...

Страница 80: ...upper limit frequency will decrease 0 70Mpa P18 31 Upper limit frequency decreasing ratio 0 00Hz 10 00Hz When the current pressure is larger than P18 30 increase 0 01Mpa corresponding upper limit fre...

Страница 81: ...nent 4 0 65535h 0 P19 09 Time for use of component 5 0 65535h 0 P19 10 Motor actual output power 0 0 6553 6kW 0 0kW P19 11 Current pressure 0 00 655 36Mpa 0 00Mpa P19 12 Current temperature 20 150 C 0...

Страница 82: ...nent 2 1 need maintenance 0 normal BIT2 tip for maintenance of component 3 1 need maintenance 0 normal BIT3 tip for maintenance of component 4 1 need maintenance 0 normal BIT4 tip for maintenance of c...

Страница 83: ...rated current or the default value P02 00 1 P02 00 0 P02 15 P02 19 P02 01 P02 05 P00 15 2 RUN 3 Press QUICK JOG for jogging and check the direction If the direction is incorrect change the wiring of t...

Страница 84: ...fault FR Pay attention to the rotation direction of the fan Master Inverter Note a The one key to set key is available once wiring is done according to above diagram b PT100 of GD300 01 in above diag...

Страница 85: ...tection signal E stop Note a The one key to set key is available once wiring is done according to above diagram b PT100 of GD300 01 in above diagram is selected by P18 03 It is set as temp detection t...

Страница 86: ...yer as the grounding wires during RS485 remote communication In the cases with less devices and shorter distance it is recommended to use 120 terminal resistor as the performance will be weakened if t...

Страница 87: ...ain inverter state information as well as relevant inverter parameter setting Function instruction Address definition Data meaning instruction R W characteristic Communication control command 2000H 00...

Страница 88: ...rohibited W R 200AH Virtual input terminal command range 0x000 0x1FF W R 200BH Virtual output terminal command range 0x00 0x0F W R 200CH Voltage setting value specific for V F separation 0 1000 1000 c...

Страница 89: ...5535 W 2016H Working time of part 2 0 65535 W 2017H Working time of part 3 0 65535 W 2018H Working time of part 4 0 65535 W 2019H Working time of part 5 0 65535 W 201AH Running time of the device 0 65...

Страница 90: ...H R AI 4 300FH R Read high speed pulse 1 input 3010H R Read high speed pulse 2 input 3011H R Read current step number of the multi step speed 3012H R External length value 3013H R External counting va...

Страница 91: ...r PC is writing or reading and the user password is set without password unlocking it will report that the system is locked The slave uses functional code fields and fault addresses to indicate it is...

Страница 92: ...ity switch The indicator of proximity switch flickers after inverter starts overturn occurred to output level by mistake Solution Check and confirm the sensor feedback line is routed with motor cable...

Страница 93: ...grounding terminal PE of the inverter B 3 Unable to stop or indicator shimmering caused by coupling of motor cable Interference phenomena Unable to stop For inverter system whose start stop is control...

Страница 94: ...c Try to change the modulation mode to 3 phase modulation and two phase modulation P8 40 00 Solution to mal operation of RCD on the part of system distribution a Check and confirm the power cable is...

Страница 95: ...te grounding the shell of inverter cabinet by power GND or ground pile b If there is no ground connection on site it is necessary to electrically connect the motor shell with grounding terminal PE of...

Страница 96: ...201707 V2 1 6 6 0 0 1 0 0 1 9 0...

Отзывы: