Goodrive300-01 inverter for air compressor Function parameters
-41-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
COM
SB2
SB1
FWD
REV
SIn
SB3
Sln
FWD
REV
Direction
ON
OFF→ON
ON
Forward
OFF
Reverse
ON
ON
OFF→ON
Forward
OFF
Reverse
ON→OFF
Decelerate
to stop
Note
:
for the 2-wire running mode, when FWD/REV
terminal is valid, the inverter stop because of the
stopping command from other sources, even the
control terminal FWD/REV keeps valid; the inverter
won
’
t work when the stopping command is
canceled. Only when FWD/REV is relaunched, the
inverter can start again. For example, the valid
STOP/RST stop when PLC signal cycles stop,
fixed-length stop and terminal control (see P07.04).
P05.14
Switch-on delay
of S1 terminal
The function code defines the corresponding delay
time of electrical level of the programmable terminals
from switching on to switching off.
The setting range: 0.000~50.000s
0.200s
○
P05.15
Switch-off delay
of S1 terminal
0.200s
○
P05.16
Switch-on delay
of S2 terminal
0.000s
○
P05.17
Switch-off delay
of S2 terminal
0.000s
○
P05.18
Switch-on delay
of S3 terminal
0.000s
○
P05.19
Switch-off delay
of S3 terminal
0.000s
○
P05.20
Switch-on delay
of S4 terminal
0.000s
○
P05.21
Switch-off delay
of S4 terminal
0.000s
○