Goodrive300-01 inverter for air compressor Function parameters
-43-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
P05.41
AI2 input filter
time
Input filter time: The parameter is used to adjust the
sensitivity of the analog input. Increasing the value
properly can enhance the anti-interference of the
analog, but weaken the sensitivity of the analog
input.
Note: Analog AI1 and AI2 can support
0~10V/0~20mA input, when AI1 and AI2 selects
0~20mA input, the corresponding voltage of
20mA is 10V. AI3 can support the output of
-10V~+10V.
The setting range of P05.32: 0.00V~P05.34
The setting range of P05.33: -100.0%~100.0%
The setting range of P05.34: P05.32~10.00V
The setting range of P05.35: -100.0%~100.0%
The setting range of P05.36: 0.000s~10.000s
The setting range of P05.37: 0.00V~P05.39
The setting range of P05.38: -100.0%~100.0%
The setting range of P05.39: P05.37~10.00V
The setting range of P05.40: -100.0%~100.0%
The setting range of P05.41: 0.000s~10.000s
The setting range of P05.42: -10.00V~P05.44
The setting range of P05.43: -100.0%~100.0%
The setting range of P05.44: P05.42~P05.46
The setting range of P05.45: -100.0%~100.0%
The setting range of P05.46: P05.44~10.00V
The setting range of P05.47: -100.0%~100.0%
The setting range of P05.48: 0.000s~10.000s
0.100s
○
P05.42
Lower limit of
AI3
-10.00V
○
P05.43
Corresponding
setting of the
lower limit of AI3
-100.0%
○
P05.44
Middle value of
AI3
0.00V
○
P05.45
Corresponding
middle setting of
AI3
0.0%
○
P05.46 Upper limit of AI3
10.00V
○
P05.47
Corresponding
setting of
the upper limit of
AI3
100.0%
○
P05.48
AI3 input filter
time
0.100s
○
P05.49, P05.50, P05.51, P05.52, P 05.53 and P05.54 are reserved.
○
P06 Group Output terminals
P06.00
Reserved
P06.01 Relay RO3 output 0: Invalid
1: In operation
2: Forward rotation operation
3: Reverse rotation operation
4: Jogging operation
5: Inverter fault
6: Frequency degree test FDT1
7: Frequency degree test FDT2
0
○
P06.02 Relay RO4 output
0
○
P06.03 Relay RO1 output
27
○
P06.04 Relay RO2 output
28
○