Goodrive300-01 inverter for air compressor Product overview
-7-
Function
Specification
Fault protection
Provide more than 30 fault protection functions: overcurrent,
overvoltage, undervoltage, overheating, phase loss and
overload, etc.
Restart after rotating
speed tracking
Smooth starting of the rotating motor
Peripheral
interface
Terminal analog input
resolution
< 20mV
Terminal switch input
resolution
< 2ms
Analog input
2 (AI1, AI2)0~10V/0~20mA, 1 (AI3)-10~10V
Analog output
2 (AO1, AO2)0~10V /0~20mA
Temperature signal
detection
3-wire PT100 signal input, -20~150°C
Digital input
8 common inputs, the Max. frequency: 1kHz, internal
impedance: 3.3
kΩ;
1 high speed input, the Max. frequency: 50kHz
Relay output
2 programmable NO outputs, 2 programmable NO/NC outputs
Contact capacity: 3A/AC250V, 1A/DC30V
Others
Installation manner Wall, floor and flange mounting
Temperature of the
running environment
-10~50°C, derate above 40°C
Protection level
IP20
Pollution level
2
Cooling mode
Air-cooling
Braking unit
Built-in for inverters of 380V (
≤30kW)
External for others
EMC filter
Built-in C3 filter: meet the degree requirement of IEC61800-3
C3
External filter: meet the degree requirement of IEC61800-3 C2
2.2 Nameplate
Note: It is the example of Goodrive300-01 standard name plate format and the CE\TUV\IP20