Goodrive300-01 inverter for air compressor Function parameters
-74-
Function
code
Name
Detailed instruction of parameters
Default
value
Modif
y
LED tens:
0: Communication encrypting invalid
1: Communication encrypting valid
P17 Group Monitoring function
P17.00
Set frequency
Display current set frequency of the inverter
Range: 0.00Hz~P00.03
0.00Hz
●
P17.01 Output frequency
Display current output frequency of the inverter
Range: 0.00Hz~P00.03
0.00Hz
●
P17.02
Ramp reference
frequency
Display current ramp reference frequency of the
inverter
Range: 0.00Hz~P00.03
0.00Hz
●
P17.03
Output voltage
Display current output voltage of the inverter
Range: 0~1200V
0V
●
P17.04
Output current
Display current output current of the inverter
Range: 0.0~3000.0A
0.0A
●
P17.05
Motor speed
Display the rotation speed of the motor
Range: 0~65535RPM
0RPM
●
P17.06
Torque current
Display current torque current of the inverter
Range: 0.0~3000.0A
0.0A
●
P17.07
Exciting current
Display current exciting current of the inverter
Range: 0.0~3000.0A
0.0A
●
P17.08
Motor power
Display current power of the motor. 100.0%
corresponds to the rated power of the motor. The
positive value is in electromotion state while the
negative value is in power generating state.
Setting range: -300.0%~300.0% (motor rated power)
0.0%
●
P17.09
Output torque
Display the current output torque of the inverter.
100.0% corresponds to the rated torque of the
motor. During FWD rotation, the positive value is in
electromotion state while the negative value is in
power generating state. During REV rotation, the
states are on the contrary.
Range: -250.0~250.0%
0.0%
●
P17.10
Evaluated motor
frequency
Evaluate the motor rotor frequency on open loop
vector
Range: 0.00~ P00.03
0.00Hz
●
P17.11
DC bus voltage
Display current DC bus voltage of the inverter
Range: 0.0~2000.0V
0V
●