INTEC GmbH
22/12/2016
Lift controller MLC 8000
Operating manual V2.0
46/196
1. Menu level
2. Menu level
3. Menu level
4. Menu level
Description
completely pulled in /pulled out.
- both on: The door close relay remains on after the door is completely
closed; the door open relay remains energized after the door is fully
opened
- both off: Once the holding bolts are completely in / out, the relays are
switched off immediately.
- Out on: The relay to pull out the holding bolts remains energized
even if the holding bolts are completely pulled out and is switched off
not until the holding bolts should be pulled in.
- In on: The relay to pull in the holding bolts remains energized even if
the holding bolts are completely pulled in and is switched off not until
the holding bolts should be pulled out.
- Both on: Both relays remain switched on even if the assigned state is
reached.
In-out[ms]
Delay time between changing the moving direction of holding bolts
(pull in / pull out).
Max.time[s]
Supervision time for pulling in / out the holding bolts. If the bolt doin't
reached attached position the lift controller sets an error message.
Max.Bolt in
Max. Number of attempts to pull in the holding bolt before going out of
operation.
Max.Bolt out
Max. Number of attempts to pull out the holding bolt before going out
of operation.
Errordel[ms]
Debouncing time for the holding bolt contacts to prevent error
messages.
Startdel[ms]
Start delay to move upwards / downwards for handling the holding
bolts.
Bolt if fire
Indicates if the holding bolts must be used in case of fireman
operation.
Floors with Hold
Indicates which floors are equipped with holding bolts.
1. Floor
1st floor is equipped with holding bolts (yes / no)
2. Floor
2nd floor is equipped with holding bolts (yes / no)
...
Deceler.check
Parameter for Slow down supervision when driving into the end floor
v-lim.[mm/s]
speed threshold at which the special exit "v-limit" is turned on or off.
Slow speed
Reduced speed to which delays should be applied when entering the
top or bottom floor (v1 or v2)