INTEC GmbH
22/12/2016
Lift controller MLC 8000
Operating manual V2.0
58/196
1. Menu level
2. Menu level
3. Menu level
4. Menu level
Description
Overl[kg]
Starting this value is detected as overload.
Setting this value to 0, the overload detection is disabled.
Temp.sensor
Settings for temperature sensor on HSE board (only HSE version 1.05
and newer)
Min.temp
Use temperature sensor for checking minimum machine room
temperature
Min.Limit[°C]
Minimum temperature in °C
Max.temp
Use temperature sensor for checking maximum machine room
temperature
Max.Limit[°C]
Maximum temperature in °C
Cooling [°C]
Temperature level to switch on cooling (Special output-cooling; e.g.
for control cabinet fan)
Internal Param.
All red values are system parameters and should be changed only in
exceptional cases by specialists.
Empty load
Analog value of the load sensor in an empty car.
100% load
Analog value of the load sensor with a full car (rated load).
Startpos.
Internal starting value for position count
Count dir.
Counting direction of the position sensor (Encoder)
Doorzone> >SGM
Simulation of the door zone switch by controlling (distance between
the simulated signal SGO and SGU and switching point SGM)
Min.
Doorzone>
Settings for lifts with very short floor distances (<300mm approx): If
the floor distance is less than the this value, then the two floors have a
common door zone; which means, the door zone between the two
floors is not switched off (both "real" door zone switch as well as
simulated by the lift controller or "Double-AWG" door zone switch)
Inc.by accu
Setting if the incremental position encoder is buffered by battery
voltage or not. If set to "No", a new calibration trip (reset trip) takes
place (to the reference switch SGE) if the mains supply was switched
off. If set to "Yes", it is assumed that the incremental encoder counts
up even during a power failure and thus a new calibration run is not
required.
AWG1-2[mm]
In case of usage a "Double AWG" for positioning: distance between
the two position units and thus the difference in the measured
position.
Pos.mode[mm]
Only for operation of a CANopen Lift frequency inverter in "Position
mode": distance from the required braking point when entering a level
in which the targeted floors can still be changed.