INTEC GmbH
22/12/2016
Lift controller MLC 8000
Operating manual V2.0
121/196
After switching on the power again, the HSE tests if there is a valid parameter set in the
EEPROM. If not, then following message appears " No actual parameter set! Load
default:ENT, Skip ESC ".
This message can have 3 different reasons:
- The EEPROM is actually empty or defective
- The two EEPROMs are reversed when changing
- There is a new HSE used with a different (newer) software version
If pressing ENTER, all parameters are checked for validity. All parameters that are within
their valid range are retained, all other parameters (for example, all in a new software version
newly added parameters) are set to a default value.
If, after the next reboot of the HSE (on / off voltage or reset button), this message appears
again, then the EEPROM is probably faulty.
Important note: When changing the HSE or replacing defective relays only relays
with 2 changeover contacts must be used!
7.6 Parameters for freely programmable inputs and outputs
Almost all inputs and outputs of the lift controller MLC 8000 are freely programmable and
have no fixed function.
The function of the inputs and outputs can be set by parameters via the keyboard of the HSE
or the hand-held terminal. It does not matter in most cases (exceptions: see description of
the relevant function) whether the input or output function is set for the HSE, the FVE or for
an ESE or TSE board.
There are only a few functions that can only be set to specific modules (e.g. drive
speed signals can only be programmed for ASE and HSE). Even it is possible to
programm such functions like speed signals to a FVE - they will not work.
A parameter for an input or output consists of 6 sub parameters:
- Main function
Fct
- Sub function
Sub
- Lift
Lift
- Floor
Floor
- Door
Door
- Switching Logic
Logic
Depending on the selected main function only the necessary sub parameters will be
displayed (for example if "Load" is selected as main function, the sub parameter "Door" is not
necessary and will not be displayed).
The sub parameter "Lift" is only displayed, if the input or output is programmed for an ESE
parameter.
Sometimes the name of any sub parameter is changed depending on the selected main
function (for example if "Land.call" is selected as main function, the name of the sub function